Just Corporation TGMJ Indicating Temperature Controller

Product Made in Japan
Manufacturer: Just Corporation
Model: TGMJ

Product Summary

Multiple inputs for any sensor
PID auto-tuning function
PID self-tuning function
*Upper and lower limit alarms are standard equipment
There are three control output models: relay contact, non-contact voltage (SSR), and direct current (4 to 20 mA output)
Simple timer function
PC communication function (500m MAX, 31 devices can be connected)

Appearance and Dimensions

TGMJ

Specification

Control OutputPlease select when ordering.
* Relay contact output
AC 250V 3A (resistive load) 1a contact
* SSR drive voltage output
DC 0-12V (load resistance 600Ω or more)
* Current output
DC 4-20mA (resistive load 600Ω or less)
Alert●Alarm 1, 2 (with upper and lower limits)
●Control action….ON-OFF
●Control action….ON-OFF action gap 1°C
Control Action●PID auto-tuning function
●PID self-tuning function

■ Rating

Voltage100 to 240V (allowable fluctuation range 85 to 264)
power consumption10VA (max.)
Ambient temperature and humidity0 to 50°C/35 to 85%

■Material

Outer casePolycarbonate
PaintingLight gray
Weight180g

■ Settings and instructions

accuracy±0.3% F.S.
Setting methodFlat Key
Display method: Numeric displayNumeric display: 7-segment LED, 3 digits

■ Terminal arrangement

TGMJ

■ Input

・Constant input signal: Select one from the following inputs

– Input range: Simple programmable range

Input Typerange
No decimal pointsWith decimal point
1, Pt1001, -199 to 500°C2, -199.9~500.0℃
2,K(CA)2, -200 to 1372°C4. -199.9 to 999.9℃
3,J(IC)3. -200 to 850°C6. -199.9 to 850℃

■ Product Number

Part numberSensor input No. *1Range No. *2
Relay Contact OutputTGMJR( )( )
SSR drive voltage outputTGMJS( )( )
Current OutputTGMJA( )( )

 

■Please use correctly

Power outage handling
Power Outage Detection: Control stops when power outage is detected
Power outage: Setting values, PID parameters, etc. are stored in non-volatile memory
When power is restored: Automatic start
self-diagnosis
Calculation and control abnormalities:Watchdog timer monitoring
Sensor input abnormality, disconnection: Control stops, operation output reaches upper/lower limit

REQUEST QUOTATION

PAYMENT

payment-methods

Return Top