NOHMI BOSAI
NOHMI BOSAI FRRJ001-Y-4F/FRRJ001-Y-16F Initiating Device Module

Manufacturer: NOHMI BOSAI
Product name: ADDRESSABLE MODULE FOR INITIATING DEVICES (4-ADDRESS TYPE & 16-ADDRESS TYPE)
Model: FRRJ001-Y-4F/FRRJ001-Y-16F
Features of FRRJ001-Y-4F/FRRJ001-Y-16F
- 4 & 16 consecutive addresses per unit
- NFPA Class A (Styles 6 & 7) and Class B (Style 4) for SLC
- NFPA Class B (Style B) for IDC
- Electronic address setting
- Slim unit
- Easy installation
Description
- The Addressable Module for Initiating Devices 4-address type and 16-address type are used to supervise the status of conventional initiating devices connected on each initiating device circuit (IDC). 4 consecutive addresses can be configured to FRRJ001-Y-4F per unit, and 16 consecutive addresses can be configured to FRRJ001-Y-16F per unit.
- The FRRJ001-Y-4F and FRRJ001-Y-16F detect alarm conditions and report to the Fire Alarm Control Panel (FACP). The IDC wiring style is applicable to the NFPA Class B (Style B). When the FRRJ001-Y-4F or the FRRJ001-Y-16F detects an alarm, the module is latched until the system is reset.The FRRJ001-Y-4F and the FRRJ001-Y-16F are slim units, and they can be installed easily.
Specifications of FRRJ001-Y-4F/FRRJ001-Y-16F
| No. | Item | Specification |
|---|---|---|
| 1 | Rated voltage of SLC input power (S+, S-) | 24.0V |
| 2 | Maximum current consumption of SLC (S+, S-) | 250µA |
| 3 | Applicable SLC wiring style | NFPA Style 4, 6, and 7 |
| 4 | Operating voltage of external power supply line (PF, PF0) | 24.0V |
| 5 | Rated output voltage of IDC (C, L) | 24.0V |
| 6 | Maximum module standby current of IDC 24VDC (C, L) | FRRJ001-Y-4F: 1.50mA, FRRJ001-Y-16F: 6.40mA |
| 7 | Maximum detector standby current of IDC 24VDC (C, L) | 1.35mA |
| 8 | Maximum module and detector alarm current of IDC 24VDC (C, L) | 30mA |
| 9 | Applicable IDC wiring style | NFPA Style B (i.e. Class B) |
| 10 | Number of addresses per unit | FRRJ001-Y-4F: 4 addresses, FRRJ001-Y-16F: 16 addresses |
| 11 | Maximum wiring resistance of IDC (C, L) | 50Ω |
| 12 | Maximum wiring capacitance of IDC (C, L) | 1µF |
| 13 | End-of-line device for IDC (C, L) | Model no. FZE016A |
| 14 | Operating temperature range | -10°C to 50°C (14°F to 122°F) |
| 15 | Operating relative humidity range | 20 to 85% (non-condensing) |
| 16 | Dimensions | FRRJ001-Y-4F: 68mm (2.68 inches) (H) x 34mm (1.34 inches) (D) FRRJ001-Y-16F: 68mm (2.68 inches) (H) x 74mm (2.91 inches) (D) |
Compatible Conventional Detectors
| Series/Model Number | Type | Maximum connectable number |
|---|---|---|
| FDS01U | Ionization | 20 units |
| FDS226 series | Ditto | 30 units |
| FDS240 series | Ditto | 30 units |
| FDK01U | Photoelectric | 20 units |
| FDK101U | Photoelectric with fixed heat | 20 units |
| FDK226 series | Photoelectric | 30 units |
| FDK229 series | Ditto | 20 units |
| FDK246 series | Ditto | 30 units |
| FDK282 series | Ditto | 20 units |
| PSD7155D | Ditto (Product of Kidde-Fenwal) | 20 units |
Installation
Figure 1: Installation in an electrical enclosure
Wiring Diagram
Figure 2: Wiring diagram of FRRJ001-Y-4F