Miyawaki GH70D Ball Float Steam Traps

Manufacturer: MIYAWAKI Inc.
Model: GH70D

Features

Quick startup
An internal air vent automatically discharges the initial air and cold condensate. The diaphragm air vent follows the saturation temperature and prevents air and steam locking.

Suitable for medium to high capacity steam processes
Adjust the degree of valve opening according to volume of condensate generated to provide maximized heat exchange capacity.

Condensate recovery
With a high degree of back pressure tolerance, this model supports condensate recovery.

Easy maintenance
For quick and easy maintenance, all valve parts are attached to the cover, making maintenance easy. The trap can be serviced directly in line.

High discharge capacity
A double ported balance valve provides a large discharge capacity in comparison with single valve models.

Typical applications

Suitable for use in industrial plant systems, foodstuff devices, and dyeing/cleaning devices.

Dimensions/Weight

SizeDimensions (mm)Dimensions (in)Weight
LH1H2W1W2LH1H2W1W2(kg)(lb)
3″38018040010557015.07.115.84.122.4172379.3
4″

*Available flange standards: ASME/JPI 150lb, 300lb, DIN PN40, JIS 10K, 16K, 20K
*Customized face-to-face dimensions on request.
*Please contact MIYAWAKI for further information.

Specifications

ModelConnectionMax. operating

pressure

Max. operating differential

pressure

Max. operating

temperature

Air vent

type

Body

material

TypeSizePMO

(MPa)

PMO

(psig)

⊿PMX

(MPa)

⊿PMX

(psig)

TMO

(℃)

TMO

(℉)

GH70D-21FFlanged

FF,RF*

3″2,13052,1305220428DiaphragmCast steel

SCPH2/WCB

4″

*Available flange standards: ASME/JPI 150lb, 300lb, DIN PN40, JIS 10K, 16K, 20K

The maximum allowable pressure (PMA) is set at 4.0 MPa (580 psig), and the system allows a maximum temperature (TMA) of 400°C (752°F). Moreover, the maximum operating back pressure (PMOB) reaches 90% of the pressure on the inlet side, ensuring optimal performance under specified conditions.

*ASTM material (WCB) on request.

This product uses a double ported balance valve system so if the actual condensate volume is significantly lower than the product’s discharge capacity, there may be a steam leak.

Discharge Capacity

GH70D