Multi Measuring Instruments Co.
Multi MCL-800IR Large Diameter φ80mm Io/Ior Clamp Leaker

Manufacturer: Multi Measuring Instruments Co., Ltd.
Model: MCL-800IR
Features
- Insulation resistance display range: 0.001 MΩ to 9.999 MΩ
- Minimum resolution of 0.001 mA achieved by adopting ultra-high-precision CT
- First integrated large-diameter clamp designed for precise measurement
Specifications
Current Consumption | Approx. 14mA |
---|---|
Operating Circuit Voltage | AC 500V or less (on insulated wires) |
Withstand voltage | AC 2000V, 1 minute (between the CT and grip sections) |
power | AA Alkaline Batteries LR03×3 |
Battery life | Approx. 48 hours (with continuous use) |
Temperature and humidity | 0~40°C 80%RH or less (however, it must be non-condensing) |
Dimensions and weight | W71XH315XD37mm Approx. 750g |
Measurement Functions | Leakage Current (Io), Line Current (I), Resistance Minute Leakage Current (Ior), Voltage (V), Insulation Resistance (MΩ) [Calculated Value] |
Measurement method | CT clamping method (measured by voltage reference during Ior measurement) |
Measuring range | Leakage Current (Io) / Line Current (I): 0~10A 4 range auto Minimum resolution 0.001mA |
Resistance Leakage Current (Ior): 0~10A 4 Range Auto Minimum Resolution 0.001mA | |
Voltage (V): 10V~500V 1 range Minimum resolution 0.1V | |
Insulation Resistance (MΩ): 0.001MΩ~9.999MΩ | |
accessory | AA alkaline battery (internal to the main unit), voltage sucking leads, mobile case, instruction manual |
Auto Power Off | Auto power off in about 10 minutes after power on |
Overrange display | “OL” mark lit |
Data Hold | “DH” mark lit |
Battery Low Indicator | “Battery” mark lit |
AC conversion method | Methodical comparison |
Sample Rate | 2 times / sec |
indication | LCD display, up to 9999 counts, unit symbol |
Input Frequency | 50/60Hz (manual switching) |
AC detection system | Mean Effective Value Conversion |