Multi Measuring Instruments Co.
Multi MCM-8000 Multi-Circuit RCD Monitor

Manufacturer: Multi Measuring Instruments Co., Ltd.
Model: MCM-8000
Features
・Measurement and recording of leakage current for up to 8 circuits
at the same time ・Trigger record to record the date and time of leakage occurrence/end of leakage current/maximum leakage value when the set current value is exceeded
・Logging record to record the average leakage value between set intervals
・Power outage record to record when the AC adapter runs out of charge
・A wide lineup of current sensors (optional)
・High-speed sampling of about 20ms
・Alarm output function that outputs a voltage-free contact when the set current value is exceeded
・The recorded data is stored inside the main unit in CSV format and can be displayed on a PC with the included software, and the trigger recorded data can also be checked on the main unit display
Specifications
Number of Measurement Circuits | 8 circuits |
---|---|
Measuring range | AC 0~2000mA |
Minimum resolution | 1mA |
AC current accuracy | ±3%rdg±2dgt |
Sample Speed | Approx. 20ms |
Filter characteristics | Built-in high-frequency cut filter |
Set current value | 1mA intercalation in 10~1000mA |
Measurement Interval | Choose from 1/5/10/15/30/60 minutes |
memory capacity | Trigger Records: Approx. 2,000 Data Logging Logs: Approx. 32,000 Data Power Outage Logs: 4000 Data |
Software Compatible OS | windows Vista / 7 / 8 / 8.1 / 10 / 11 |
power | Rechargeable NiMH battery or AC adapter |
Dimensions and Weight | W190×H140×D42mm Approx. 700g |
accessory | Carrying case, AC adapter, RS232C cable, communication software |
option | ZCT-18SCM CT Inner Diameter φ18mm ¥14,000 (excluding tax) ZCT-30SCM CT Inner Diameter φ30mm ¥17,500 (excluding tax) ZCT-40SCM CT Inner Diameter φ40mm ¥21,500 (excluding tax) ZCT-80SCM CT Inner Diameter 74×80mm ¥32,500 (excluding tax) ZCT-1100SCM CT Inner Diameter 108×128mm ¥73,000 (excluding tax) All CT leads: 5m CT storage case (MK-001) ¥ 10,500 (excluding tax) |