I.T.O Corporation
ITO (T)AX-50A/ AHL 50kg/h Double Stage Automatic Changeover Regulators

Manufacturer: I.T.O Corporation
Model: (T)AX-50A/ AHL
Model Reference Guide
- AX-50A Model Code
- TAX-50A Model Code
- AX-50AHL Model Code
- TAX-50AHL Model Code
①Outlet Connection
![]() | ![]() |
![]() | ![]() |
①
Code | Outlet Connection | ||
---|---|---|---|
(T)AX-50A | (T)AX-50AHL | ||
Rc1 1/4 Union | ![]() | ![]() | |
With BV | BV-32U Rc1 1/4 Ball Valve for Union | ![]() |
*BV-32U provided with kit, not assembled.
Range Specification
Capaciy(Propane) | 50kg/h |
---|---|
Inlet Pressure | 0.10~1.56MPa |
Outlet Pressure | 2.55~3.30kPa |
Lockup Pressure | ≤3.50kPa |
Safety Relief Valve Working Pressure | 5.60~8.40kPa |
Starting Pressure of Replenishment | < 0.10MPa |
Inlet Connection | JIS20K20A Flange |
Accessories
![]() |
20A Flange Gasketx2* *Bolts, nuts and washers are not included. |
Model Reference Guide
*If the specification you require is not offered in the table below, contact our local branch or agency.
ACO Without Leakage Detecting System | |
ACO without Signal Transmitting Function | ACO with Signal Transmitting Function |
---|---|
Model | Model |
AX-50A | TAX-50A |
AX-50A(with BV) | TAX-50A(with BV) |
ACO Incorporating Leakage Detecting System | |
ACO without Signal Transmitting Function | ACO with Signal Transmitting Function |
---|---|
Model | Model |
AX-50AHL | TAX-50AHL |
*See page 97 regarding gas flow recorders.