I.T.O Corporation
ITO CV/ IV/ CP Emergency Shut-Off System


Manufacturer: I.T.O Corporation
Model: CV/ IV/ CP
Operating Pressure
| Model | Pressure Range | |||||
|---|---|---|---|---|---|---|
| 0.30MPa | 0.50MPa | 0.70MPa | 1.00MPa | 1.50MPa | 2.00MPa | |
| CV-15F~CV-40AF | 0.10MPa | 0.11MPa | 0.13MPa | 0.15MPa | 0.20MPa | 0.25MPa |
| CV-50AF | 0.10MPa | 0.13MPa | 0.15MPa | 0.20MPa | 0.30MPa | 0.35MPa |
*Use compressed air or nitrogen for the impulse line.
Air-Acutuated Shut-Off Valve
![]() | ![]() | ![]() | |||
| Connection: JIS20K15A Flange | Connection: JIS20K20A Flange | Connection: JIS20K25A Flange | |||
![]() | ![]() | ||||
| Connection: JIS20K40A Flange | Connection: JIS20K50A Flange | ||||
For the SOV Control Orifice Valve

*Use for reset.
Blow Valve

*Use for manual shut-of
Earthquake-Actuated Sensor

| Model | CP-400B |
|---|---|
| Vibration Acceleration | 320~400gal |
| Vibration Frequency | 1.4~3.3Hz |
| Tripping Method | Steel Ball Dropping Type +Magnet & Heavy Bob Dropping Type |
| Operating Pressure Range | 0.10~0.35MPa |
| Activation Display | Pressure Gauge |
| Reset Method | Manual Operation by the Reset Lever |
| Installation Method | Ground Line Installation |
| Connection | Copper Pipe(φ8 Outer Diameter) |
*Use compressed air or nitrogen for the impulse line.