Shimaden CP3701 Thermocouple Temperature Converter

Manufacturer: SHIMADEN CO., LTD.
Model: CP3701

Features

The thermocouple input signal is converted into various DC signals and output. It is an isolation output thermocouple temperature converter.

Specification

Input Types:
Thermocouple: 8 types
T, E, J, K, N, R, S, B
Output Types:
0–10mV DC
0–100mV DC
-10–10mV DC
-100–100mV DC
1–5V DC
4–20mA DC
0–5V DC
0–10V DC
Conversion Accuracy:
±0.1% FS ±0.5°C + Linearization accuracy
Linearization Accuracy: 0.1% FS (typical)
Reference Junction Temperature Compensation:
Built-in temperature compensator (temperature-sensing element)
Input Resistance:
≥1MΩ
External Resistance Tolerance:
≤1kΩ
Response Time:
≤160ms
Output Load:
1V span or higher: Load current ≤ 2mA
10mV span or higher: Load resistance ≥ 10kΩ
100mV span or higher: Load resistance ≥ 100kΩ
First output only (current): Load resistance ≤ 750Ω
Both first and second outputs (current):
First output: Load resistance ≤ 550Ω
Second output: Load resistance ≤ 350Ω
General Specifications:
Power Supply:

100–240V ±10% AC, 50/60Hz
24V DC ±10%
Power Consumption:
100–240V AC: ≤ 7VA
24V DC: ≤ 2W
Operating Conditions:
Temperature: -5 to 55°C
Humidity: ≤ 90% RH (without condensation)
External Dimensions:
H86×W29×D125 mm
Weight:
Approx. 120g (main unit)
Approx. 80g (socket terminal block)

REQUEST QUOTATION