Product nameFlame sensor with automatic fire extinguishing function for switchboards and control panels
ModelSKH089 MO-1 / MO-2
Input voltageDC 24V (SKH089MO-1) /
DC 24V or AC 85 to 240V (SKH089MO-2)
wiring14-pole screw terminal block
Current consumptionStandby: 25mA or less Detection: 90mA or less
Ambient temperature-10℃ to +60℃ (no condensation)
Detection MethodUltraviolet detection method (detection wavelength: 185nm to 260nm)
Detection distanceDetects flames of approximately 2 cm at a distance of 10 m
Detection AngleDetects diffuse reflection of ultraviolet light generated inside distribution boards and control panels 
Detection timer function0.5s, 1s to 31s in 1 second increments (switchable with the DIP switch on the main unit)
Factory default setting: 4s
Flame Detection Output2c relay contact
AC250V 5A (resistive load) DC24V 5A (resistive load)/starting device ON output
Alarm output holding functionOutput hold time: Approximately 30 seconds
*The alarm output will turn off after approximately 30 seconds when ultraviolet light is no longer detected.
Monitoring locationInside storage boxes for power distribution boards, control panels, etc. (fixed with DIN rails)
Operation indicator light (main body LED)Blue LED on, red LED off: Standby
Blue LED on, red LED on: Flame detected
External dimensionsW125mm x D90mm x H190mm (with one cylinder)
massApproximately 1,100g (1 cylinder)
Case materialFlame sensor: flame-retardant ABS (UL94) Starter: iron
Fire extinguishing agentcarbon dioxide
Cylinder sizeC60
CO₂ amount60g
Protective volume (Fire Service Act standard)0.05 m3 per bottle
CO₂ concentration 35% standard (safety rate 1%)0.086 m3 per bottle
Number of linked cylindersUp to three units can be linked together
Alarm output (wired)2c relay contact
AC250V 5A (resistive load) DC24V 5A (resistive load)
Alarm output (wireless)
Output System
Communication Function
I/O ports