Hakaru C2R CC-Link Signal Converter With Single-Point Resistance Thermometer

Manufacturer: HAKARU PLUS CORPORATION
Model: C2R

Specifications

For details other than the following, please refer to the series specifications.

Overview

This is a signal converter that amplifies, linearizes, and isolates the resistance change of an RTD, then transmits it to the CC-Link master station.

Application Examples

  • Isolates analog signals and inputs them to the sequencer.
  • Analog measured value output can be displayed on a local indicator.
  • Input and output of PLC PID instructions can be connected to a single C2R.

Model

C 2 R – (1)(2) – (3)

(1)

InputDescription
1JPt100Ω
3Pt100Ω
6Ni508.4Ω

(2)

Output
0None
Measured Value OutputRemote Output
4 : 0 to 10VV4 : 0 to 10V
5 : 0 to 5VV5 : 0 to 5V
6 : 1 to 5VV6 : 1 to 5V
O : Specified voltage rangeVO : Specified voltage range
A : 4 to 20mAVA : 4 to 20mA
Z : Specified current rangeVZ : Specified current range

(3)

Power SupplyDescription
AAC85 to 264V / DC85 to 143V
DDC24V ±10%

How to Order Example

Model: C2R-3AVA-A
Input Range: 0 to 150°C

Input Specifications

Allowable lead wire resistance: 20Ω or less per wire
Input detection current: 1mA
Manufacturable range: -200 to +650°C, minimum span 50°C
Burnout: Upscale as standard, downscale by order specification

Output Specifications

At 1 to 5V load resistance: 500Ω or more
At 4 to 20mA load resistance: 0 to 600Ω

Installation Specifications

Power consumption: Approx. 7VA at AC100V power, approx. 6W at DC100V power, approx. 6W at DC24V power.
Operating temperature range: -10 to +60°C
Mass: Approx. 400g

Performance

Reference accuracy: ±0.1%|
Burnout time: 10 seconds or less. Standard: Upscale burnout.
Response time: 0.5 seconds or less from 0 to 90%.

Connection Diagram

External Dimensions

Refer to Common Specifications External Dimensions A, page 2.

REQUEST QUOTATION

PAYMENT

payment-methods

LINK

koueigroup-banner1
koueigroup-banner1

Return Top