Hakaru C2M CC-Link Signal Converter Potentiometer – Single Point Type

Manufacturer: HAKARU PLUS CORPORATION
Model: C2M

Specifications

For details other than the following, please refer to the series specifications.

Overview

This is a signal converter that amplifies and isolates the resistance change of a potentiometer, then transmits it to the CC-Link master station.

Application Examples

  • Isolates analog signals and inputs them to the sequencer.
  • Analog measured value output can be displayed on a local indicator.
  • Input and output of PLC PID instructions can be connected to a single C2M.

Model

C 2 M – (1) – (2)

InputDescription
Resistance Value100Ω to 10kΩ

(1)

Output
0None
Measured Value OutputRemote Output
4 : 0 to 10VV4 : 0 to 10V
5 : 0 to 5VV5 : 0 to 5V
6 : 1 to 5VV6 : 1 to 5V
O : Specified voltage rangeVO : Specified voltage range
A : 4 to 20mAVA : 4 to 20mA
Z : Specified current rangeVZ : Specified current range

(2)

Power SupplyDescription
AAC85 to 264V / DC85 to 143V
DDC24V ±10%

How to Order Example

Model: C2M-AVA-A

Input Specifications

Minimum span: 50% or more of the input resistance.
Input range: Potentiometer from 0 to 100Ω to 0 to 10kΩ. No adjustment is required.
Detection voltage: DC0.5V
Zero adjustment: 0 to 50% of total resistance, adjustable from the front.
Span adjustment: 50 to 100% of total resistance, adjustable from the front.

Output Specifications

At 1 to 5V load resistance: 500Ω or more
At 4 to 20mA load resistance: 0 to 600Ω

Installation Specifications

Power consumption: Approx. 7VA at AC100V power, approx. 6W at DC100V power, approx. 6W at DC24V power.
Operating temperature range: -10 to +60°C
Mass: Approx. 400g

Performance

Reference accuracy: ±0.3%
Response time: 0.5 seconds or less from 0 to 90%.

Connection Diagram

External Dimensions

Refer to Common Specifications External Dimensions A.