Meidensha 5 Tier Medium Voltage Combination Starter

Manufacturer: Meidensha Corporation

Features

The flat design VMC allows a maximum of 5 stacking, reducing the footprint by approximately 60%. Medium voltage live parts are isolated with an earthed metal and a shutter made of insulating material. The insulating mold partition walls ensure vertical busbars are isolated between phases and betwen phases and earth. The multi-functional digital relay and wide range CT require only parameter adjustments for different loads, capacities and starting methods, eliminating the need for replacing CTs.
Small footprint
Safe and reliable
Flexible applications

Applications and Solutions

The small footprint allows installation in a confined space that is too small for similar products

Specifications

SpecificationsNotes
StandardJEM1225-2007
Minimum external dimensions W × H × D (mm)700 / 2350 / 1300Maintenance space requirements: 1500 for front and 600 for rear (mm)
Maximum number of tiers5 tiersCommon to both 3.3/6.6 kV
Rated system voltage (kV)3.3 / 6.6
Withstand voltage (kV)Lightning impulse (phase-to-earth, phase-to-phase): 60No. 6 A equivalent, excluding between VI poles
Lightning impulse (between isolator poles): 70
Power frequency (1 min) phase-to-earth, phase-to-phase: 22
Power frequency (1 min) between same poles of disconnector: 25
Rated frame current (A)200
Rated bus (vertical) current (A)1000Notes 2 and 3
Rated bus short-time current (kA)/(s)40 / 0.5
Rated short circuit breaking current (kA)MV electromagnetic contactor: 4
Power fuses: 40
Maximum permissible load capacity (3.3/6.6 kV)Electric motor: 710 / 1400 kWNotes 2 and 3
Transformer: 1000 / 2000 kVA
Capacitor: 750 / 1500 kvar

Notes: 1 Please contact us for details of external dimensions.
2 Load cables up to 60 sq for 5-tier design.
3 Total load current per panel should not exceed 700 A.
4 Specifications subject to change without notice.MEIDENSHA