Multi Measuring Instruments Co.
Multi MCL-500IR IO/IOR Clamp Leaker

Manufacturer: Multi Measuring Instruments Co., Ltd
Model: MCL-500IR
Features
Resistance leakage current can be measured from 0.4mA~4A
Load current can be measured from 0.02A~500A
Voltage can be measured from 0V~500V
Specifications
Current Consumption | Approx. 14mA |
---|---|
Operating Circuit Voltage | AC 500V or less (on insulated wires) |
Withstand voltage | AC 2200V, 1 minute (between the CT part and the grip part) |
power | AA Alkaline Batteries LR03×3 |
Battery life | Approx. 45 hours (with continuous use) |
Temperature and humidity | 0~40°C 80%RH or less (however, it must be non-condensing) |
Dimensions and weight | 70(W)X223(H)X34(D)mm, approx. 440g (including battery) |
Measurement Functions | Leakage Current (Io), Load Current (I), Resistance Factor Leakage Current (Ior), Voltage (V) |
Measurement method | CT clamping method (measured by voltage reference during Ior measurement) |
Measuring range | Current: 0~40mA, 400mA, 4A(I,Io,Ior) 0~40A, 500A(I) |
Voltage: 10V~500V (V) | |
accessory | AA alkaline battery (internal to the main unit), voltage sucking leads, mobile case, instruction manual |
Filter Switching | In I,Io current measurement, pressing the filter switch once displays “FL” on the indicator and cuts off the high frequency. Press again to release. The filter switch is disabled during IOR measurement. |
Auto Power Off | Auto power off in about 10 minutes after power on |
Overrange display | “OL” mark lit |
Data Hold | “DH” mark lit |
Battery Low Indicator | “Battery” mark lit |
AC conversion method | Methodical comparison |
Sample Rate | 2 times/sec |
indication | LCD display, up to 4000 counts, unit symbol |
Input Frequency | 50/60Hz (manual switching) |
AC detection system | I, Io, V: Effective value by analog operation, Ior: Effective value operation of average value rectification by synchronous detection |