ITO C/ G/ GL Range Low Pressure Regulator

Manufacturer: I.T.O Corporation
Model: C/ G/ GL Range

Incorporated: Relief, Strainer*
*C-10A, C-20, GL-50, GL-70 and G-32A only.

  • The C, G, GL range is a direct-operated regulator to reduce outlet pressure to 20kPa or less.
  • Available for type 1 or type 2 according to the inlet pressure. Type 1 for high pressure pipe line use up to 1.56MPa with a JIS 20K flanged connection at inlet, and Type 2 for medium pressure pipe line use between 0.025~0.10MPa with JIS 10K flanged connection at inlet.
Maximum Flow Rate (Nm³/h)C-10A-1: 12
C-10A-2: 18
InletRc 1/2
OutletRc 3/4 Union
Vent ConnectionRc 1/4
Strainer Mesh Gauge60 Mesh
Maximum Flow Rate (Nm³/h)C-20-1: 24
C-20-2: 37
InletType1: JIS 20K 15A Flange (RF)
Type2: JIS 10K 15A Flange (FF)
OutletRc 1 Union
Vent ConnectionRc 3/4
Strainer Mesh Gauge60 Mesh
Maximum Flow Rate (Nm³/h)GL-50-1/2: 60
GL-70-1/2: 85
InletType1: JIS 20K 25A Flange (RF)
Type2: JIS 10K 25A Flange (FF)
OutletRc 1 1/4 Union
Vent ConnectionRc 1
Strainer Mesh Gauge60 Mesh
Maximum Flow Rate (Nm³/h)120
InletType 1: JIS 20K 25A Flange (RF)
Type 2: JIS 10K 25A Flange (FF)
OutletRc 1 1/2 Union
Vent ConnectionRc 1
Strainer Mesh Gauge60 Mesh
Maximum Flow Rate (Nm³/h)245
InletType 1: JIS 20K 40A Flange (RF)
Type 2: JIS 10K 40A Flange (FF)
OutletRc 2 Union
Vent ConnectionRc 1
Maximum Flow Rate (Nm³/h)370
InletJIS 10K 50A Flange (FF)
OutletJIS 10K 80A Flange (FF)
Vent ConnectionRc 1
Maximum Flow Rate (Nm³/h)GL-400-2: 495
GL-500-2: 620
InletJIS 10K 50A Flange (FF)
OutletJIS 10K 80A Flange (FF)
Vent ConnectionRc 1

Range Specification

Regulation TypeType 1Type 2
Inlet Pressure (MPa)0.07~1.560.025~0.10
Outlet Pressure (kPa)
C-10A~GL-70
0.50~20.0 *1
Outlet Pressure (kPa)
G-32A~GL-500
0.80~20.0 *1
Lockup Pressure (kPa)≤ Set Point × 1.3

*1 Interchangeable springs are available.

Interchangeable Spring Selection

Set point range (kPa)

No.
C-10A2.30~3.601.50~2.303.60~5.507.50~10.09.00~15.0
C-201.60~3.405.00~10.09.00~15.014.0~20.00.80~1.80
GL-50
GL-70
1.00~4.003.50~10.05.00~15.010.0~20.015.0~20.0
G-32A1.30~3.700.80~1.508.00~16.03.00~10.5
G-36C
GL-300
GL-400
GL-500
1.50~3.503.20~10.51.25~2.500.80~1.508.00~16.0
No.SGX No.1 (White)
C-10A14.0~20.05.50~8.004.00~8.009.00~12.00.50~1.50
C-201.30~3.003.00~6.0016.0~20.08.00~12.00.50~1.50
GL-50
GL-70
0.30~1.005.00~20.06.00~12.0
G-32A14.0~20.02.00~8.006.00~12.0
G-36C
GL-300
GL-400
GL-500
14.0~20.03.00~6.008.00~12.0

     shows the standard spring.
     requires either a supporting diaphragm disc or a material change from the standard diaphragm disc.

Flow Rate

REQUEST QUOTATION

PAYMENT

payment-methods

Return Top