Hakaru
Hakaru C2D CC-Link Signal Converter Distributor – Single-Point Type

Manufacturer: HAKARU PLUS CORPORATION
Model: C2D

Specifications
For details other than the following, please refer to the series specifications.
Overview
This is a signal converter that supplies power to a two-wire transmitter, isolates the input signal, and transmits it to the CC-Link master station. It can also be used as an offline two-wire transmitter power supply for 4 to 20mA input.
Application Examples
- Isolates analog signals and inputs them to the sequencer.
- Analog measured value output can be displayed on a local indicator.
- Input and output of PLC PID instructions can be connected to a single C2D.
Model
C 2 D – (1) – (2)
| Input | Description |
|---|---|
| 4 to 20mA | Two-wire transmitter input |
(1)
| Output | |
|---|---|
| 0 | None |
| Measured Value Output | Remote Output |
|---|---|
| 6: 1 to 5V | V6 : 1 to 5V |
| A: 4 to 20mA | VA : 4 to 20mA |
(2)
| Power Supply | Description |
|---|---|
| A | AC85 to 264V / DC85 to 143V |
| D | DC24V ±10% |
How to Order Example
Model: C2D-AVA-A
Input Specifications
Input resistance: 250Ω ±1%
Two-wire transmitter power supply: DC24V 22mA, short-circuit protection included.
Output Specifications
At 1 to 5V load resistance: 500Ω or more
At 4 to 20mA load resistance: 0 to 600Ω
Installation Specifications
Power consumption: Approx. 7VA at AC100V power, approx. 6W at DC100V power, approx. 6W at DC24V power.
Operating temperature range: -10 to +60°C
Mass: Approx. 400g
Performance
Reference accuracy: ±0.1%
Response time: 0.5 seconds or less from 0 to 90%.
Connection Diagram

External Dimensions
Refer to Common Specifications External Dimensions A.