Meidensha 24kV And 36kV C-GIS High voltage Switchgear

Manufacturer: Meidensha Corporation
Model: 24kV And 36kV C-GIS

 Features

High reliability
Reduction of maintenance work
Consideration to safety
Reduction of environmental contamination
Small footprint
VCB operational and capable of breaking short-circuit current even under low SF6 gas pressure

Specifications

Switchgear

Switchgear modelHICLAD 20GC
Switchgear typeBGC-24
Applicable standardsIEC62271-200
Classification of switchgearSF6-insulated metal-enclosed
Service condition• Altitude < 1000m
• Ambient temperature Max 40°C, Min -5°C
• 24h average < 35°C
• Relative humidity 24h average < 95%
1 month average < 90%
Rated voltage (kV)24
Rated current (A)1250
Rated frequency (Hz)50/60
Insulation level1 min power frequency (kV rms): 50
1.2 × 50 μs impulse (kV peak): 125
Rated short-time withstand current (kA-s)25-3
Degree of protectionHV compartment: IP65
LV compartment: IP40
Gas pressureRated pressure (MPa): 0.05
Alarm pressure (MPa): 0.02
Operation of 3-position isolatorManual
Auxiliary voltageControl circuit (V): DC 30, 110, 125
Motor circuit (V): AC 220, 230, 240 / DC 110, 125

Vacuum Circuit-Breaker (VCB)

VCB modelVGC-22
Applicable standardsIEC62271-100
Rated voltage (kV)24
Rated current (A)1250
Rated frequency (Hz)50/60
Insulation level1 min power frequency (kV rms): 50
1.2 × 50 μs impulse (kV peak): 125
Rated short-circuit breaking current (kA)25
Rated short-circuit making current (kA peak)63
Rated short-time withstand current (kA-s)25-3
Operating dutyO-0.3sec-CO-3min-CO
Rated closing time (s)0.05
Rated opening time (s)0.05
Rated break time (s)0.07
Rated TRV for terminal faultRate of rise (kV/μs): 0.47
TRV peak voltage (kV): 41
Type of operating mechanismMotor charged spring

24kV, 36kV C-GIS 20GB, 30GB
Switchgear

Switchgear modelHICLAD 20GBHICLAD 30GB
Switchgear typeNBG-24BGB-36
Applicable standardsIEC62271-200
Classification of switchgearSF6-insulated metal-enclosed
Service condition• Altitude < 1000m
• Ambient temperature Max 40°C, Min -5°C
• 24h average < 35°C
• Relative humidity 24h average < 95%
• 1 month average < 90%
Rated voltage (kV)2436
Rated current (A)1250, 20001250, 2000, 2500
Rated frequency (Hz)50/60
Insulation level1 min power frequency (kV rms): 50
1.2 × 50 μs impulse (kV peak): 125
1 min power frequency (kV rms): 70
1.2 × 50 μs impulse (kV peak): 170
Rated short-time withstand current (kA-s)25-331.5-3
Degree of protectionHV: IP65
LV: IP40
HV: IP65
LV: IP40
Gas pressureRated: 0.05 MPa
Alarm: 0.02 MPa
Rated: 0.08 MPa
Alarm: 0.06 MPa
Operation of 3-position isolatorMotorized / Manual
Auxiliary voltageControl circuit: DC 30, 110, 125, 220
Motor circuit: AC 220, 230, 240 / DC 110, 125

Vacuum Circuit-Breaker (VCB)

VCB modelNVG-22VGB-33
Applicable standardsIEC62271-100
Rated voltage (kV)2436
Rated current (A)1250, 20001250, 2000, 2500
Rated frequency (Hz)50/60
Insulation level1 min power frequency (kV rms): 50
1.2 × 50 μs impulse (kV peak): 125
1 min power frequency (kV rms): 70
1.2 × 50 μs impulse (kV peak): 170
Rated short-circuit breaking current (kA)2531.5
Rated short-circuit making current (kA peak)6382
Rated short-time withstand current (kA-s)25-331.5-3
Operating dutyO-0.3sec-CO-3min-CO
Rated closing time (s)0.05
Rated opening time (s)0.05
Rated break time (s)0.07
Rated TRV for terminal faultRate of rise (kV/μs): 0.47
TRV peak voltage (kV): 41
Rate of rise (kV/μs): 0.57
TRV peak voltage (kV): 62
Type of operating mechanismMotor charged spring
Note* Other duties: O-0.3sec-CO-15sec-CO, O-0.3sec-CO-1min-CO-1min-CO are also available.

20GB, 20GC, 30GB

REQUEST QUOTATION

PAYMENT

payment-methods

LINK

koueigroup-banner1
koueigroup-banner1

Return Top