TOYO KEIKI GP and HP Series Power Factor Transducer
Product Made In Japan
Manufacturer: Toyo Keiki
Model: GP and HP Series
NHP-□1 : 1phase 2wire
NHP-□2 : 1phase 3wire
NHP-□3 : 3phase 3wire
Plug-in type makes upkeep and changes in configuration simple.
Improved reliability and greater compactness through the use of custom ICs.
JIS C 1111 AC/DC transducer 2.0 class.
Specification
INPUT | ||||||
---|---|---|---|---|---|---|
KIND | MARK | INPUT | RATED VOLT. | RATED CUR. | FREQUENCY | CONSUMPTION WATT |
1φ2W NHP-□1 |
1 | LEAD 0.5-1 – LAG 0.5 | 100V | 5A | 50Hz | Voltage input:0.5VA at 1 element Current input:0.5VA at 1 element |
2 | LEAD 0.5-1 – LAG 0.5 | 100 V | 5A | 60Hz | ||
3 | LEAD 0.5-1 – LAG 0.5 | 200V | 5A | 50Hz | ||
4 | LEAD 0.5-1 – LAG 0.5 | 200V | 5A | 60Hz | ||
9 | OTHER | |||||
1φ3W NHP-□2 |
1 | LEAD 0.5-1 – LAG 0.5 | 2X100V | 5A | 50Hz | |
2 | LEAD 0.5-1 – LAG 0.5 | 2 X100V | 5A | 60Hz | ||
3 | LEAD 0.5-1 – LAG 0.5 | 2 X200V | 5A | 50Hz | ||
4 | LEAD 0.5-1 – LAG 0.5 | 2X200V | 5A | 60Hz | ||
9 | OTHER | |||||
3φ3W NHP-□3 |
1 | LEAD 0.5-1 – LAG 0.5 | 110V | 5A | 50/60HZ | |
2 | LEAD 0.5-1 – LAG 0.5 | 220V | 5A | 50/60HZ | ||
9 | OTHER | |||||
Note : 1. 1 phase 2wire and 1 phase 3wire devices are set for a frequency of either 50Hz or 60Hz. 3phase line devices can operate at either 50Hz or 60Hz. 2. It is necessary to balance the voltage circuits of 3phase 3wire devices. However, the current will behave normally if the circuits are not balanced. | ||||||
WORKING RANGE | ||||||
Rated voltage range : 60V—240V Rated current range : 0.1 A—5A Rated frequency range : 45Hz—450Hz Input range for working range : LEAD 0.5—1—LAG 0.5 or LAG 0.5—1—LEAD 0.5 |
MARK | OUTPUT | LOAD RESISTANCE | WORKING RANGE | |||
---|---|---|---|---|---|---|
1 | - 100 ~ 0 ~ + 100 mV | 600 Ω ~ ∞ | Max. voltage output: 10V, Loading current: below 10mA Max. current output: 20mA, Loading voltage: below 11V Relationship between input and output: ・Lead side input for minus output and Lag side input for positive output are standard. ・We can also make items that allow Lag side input for minus output and Lead side input for positive output. ・We can also produce items that at LEAD 0.5~1~LAG 0.5 have-50%~-/+100%~+50% characteristics. |
|||
2 | - 1 ~ 0 ~ + 1 V | 600 Ω ~ ∞ | ||||
3 | - 5 ~ 0 ~ + 5 V | 2 kΩ ~ ∞ | ||||
4 | - 10 ~ 0 ~ + 10 V | 5 kΩ ~ ∞ | ||||
5 | 1 ~ 3 ~ 5 V | 2 kΩ ~ ∞ | ||||
6 | - 1 ~ 0 ~ + 1 mA | 0 ~ 10 kΩ | ||||
7 | - 10 ~ 0 ~ + 10 mA | 0 ~ 1 kΩ | ||||
8 | 4 ~ 12 ~ 20 mA | 0 ~ 550 Ω | ||||
9 | OTHER OUTPUT |
AUXILIARY POWER SUPPLY | |||
---|---|---|---|
MARK | USE RANGE | CONSUMPTION WATT | REMARK |
1 | DC 19—31V | approx. 3 W | Please inquire about items not listed on the left. |
4 | AC 80-264V (50/60Hz) DC 80-143V | approx. 4 VA approx. 3 W | |
9 | OTHER |
Specified Character
(1) Tolerance
±2% of output span. (Ambient temperature 23 ℃)
(2) Effect of temperature
Within ±0.5% of output span. (For 23 ℃±10℃ variations)
(3) Effect of auxiliary power supply
Within ±0.25% of output span. (For rated voltage ±10% variations)
(4) Effect of frequency
Within ±1.5% of output span. (For standard frequency ±5%
variations)
(5) Effect of input voltage
Within ±1.5% of output span. (For standard voltage ±10% variations)
(6) Effect of input current
Within±3% of output span. (For 20%-120% rated current variations)
(7) Effect of load resistance
Within ±0.05% of output span. (For load resistance range)
(8) Output ripple
Within 1%p-p of output span.
(9) Response time
Shorter than 1sec. (Time to 99% output)
(10) Dielectric strength
2000V AC,1min. (50/60Hz)
(Between input,output,auxiliary power and external case)
(11) Insulation resistance
Higher than 100MΩ at 500V megger.
(Between input,output,auxiliary power and external case)
(12) Weight
Power factor transducer may have the two types of characterristics shown below.
If no preference is specified characteristics will be as shown in 1.
Connection Diagram
DESIGNATION ITEM AT ORDER
1. TYPE AND AUXILIARY POWER SUPPLY | 2. INPUT | 3. OUTPUT |
---|---|---|
NHP—□□ | —□ | —□ |
① NHP-43-2-8
② NHP-43-9-8 INPUT : LEAD 0.5~1~LAG 0.5,115V,5A
※Power factor measurement in circuits that have tidal currents
The effectuve measurement range of NHP type power factor transducers is LEAD 0.5~1~LAG 0.5.
Does not operate normally during backward tidal current(the current supply and receeipt flow are reversed).
※When items from the NHP series are removed from their sockets,to prevent the input circuits from remaining open
a protector(diode unit ZHP-B)is fitted.
Inform us if this is not required.
※For special specification above contact a company representative.