Toyo Keiki
TOYO KEIKI EGM Series Watt Transducer
Product Made In Japan
Manufacturer: Toyo Keiki
Model: EGM Series
EGM-□1A : 1phase 2wire
EGM-□2A : 1phase 3wire
EGM-□3A : 3phase 3wire
EGM-□4A : 3phase 4wire
Lighter because plastic is used for casing.
Improved reliability and greater compactness through the use of custom ICs.
JIS C 1111 AC/DC transducer 0.5 class.
SPECIFICATION
KIND | MARK | INPUT | RATED VOLTAGE | RATED CURRENT | frequency | CONSUMPTION WATT |
---|---|---|---|---|---|---|
1φ2W EGM-□1A |
01 | 0 ~ 500W | 100 V | 5A | 50Z60HZ | Voltage input: 0.5VA at 1 element Current input: 0.5VA at 1 element |
11 | 0 ~ 1000W | 200V | 5A | 50Z60HZ | ||
99 | OTHER | |||||
1φ3W EGM-□2A |
01 | 0 ~ 1000W | 2X100V | 5A | 50Z60Hz | |
11 | 0 ~ 2000W | 2 X200V | 5A | 50Z60Hz | ||
99 | OTHER | |||||
3φ3W EGM-□3A |
21 | 0 ~ 1000W | 110V | 5A | 50Z60Hz | |
31 | 0 ~ 2000W | 220V | 5A | 50Z60HZ | ||
22 | 0 ~ 833W | 110V | 5A | 50Z60HZ | ||
32 | 0 ~ 1667W | 220V | 5A | 50Z60Hz | ||
99 | OTHER | |||||
3φ4W EGM-□3A |
21 | 0 ~ 1000W | 110ZV3V | 5A | 50Z60Hz | |
31 | 0 ~ 2000W | 220ZZ3V | 5A | 50Z60HZ | ||
22 | 0 ~ 833W | 110/V3V | 5A | 50Z60Hz | ||
32 | 0 ~ 1667W | 220ZV3V | 5A | 50Z60Hz | ||
99 | OTHER | |||||
WORKING RANGE Rated voltage range : 60V~240V Current range : 0.1A~5A Frequency range : 45Hz~450Hz Input range for working range 1 phase 2wire : Input range ceiling 40%~120% of (rated voltage x rated current) 1 phase 3wire : Input range ceiling 40%~120% of 2X (rated voltageXrated current) 3phase 3wire : Input range ceiling 40%~ 130% of [root3]X (rated voltageXrated current) 3phase 4wire : Input range ceiling 40%~120% of 3X (rated voltageXrated current) |
OUTPUT | |||
---|---|---|---|
MARK | OUTPUT | LOAD RESISTANCE | WORKING RANGE |
1 | DC 0~ 100mV | 600 Ω ~ ∞ | We also produse items not included in the output table on the left which cover the ranges below. Max.voltage output: 10V Loading current: below 10mA Max.current output: 20mA Loading voltage : below 11V |
2 | DC 0~ 1 V | 600 Ω ~ ∞ | |
3 | DC 0~ 5 V | 2kΩ ~ ∞ | |
4 | DC 0- 10 V | 5kΩ ~ ∞ | |
5 | DC 1 ~ 5 V | 2kΩ ~ ∞ | |
6 | DC 0 ~ 1mA | 0 ~ 10kΩ | |
7 | DC 0~ 10mA | 0 ~ 1kΩ | |
8 | DC 4~ 20mA | 0 ~550 Ω | |
9 | OTHER OUTPUT |
AUXILIARY POWER SUPPLY | |||
---|---|---|---|
MARK | USE RANGE | CONSUMPTION WATT | REMARK |
1 | DC 19V-31V | approx. 3 W | Please inquire about items not listed on the left. |
4 | AC 80V-264V 50/60Hz DC 80V-143V | approx. 4 VA approx. 3 W | |
9 | OTHER | ||
0 | NO ASSIST POWER SUPPLY(SELF POWER SUPLLY) | Power is supplied from VT input within the transducer. |
SPECIFIC CHARACTER
(1) Tolerance
±0.5% of output span. (Ambient temperature 23 ℃)
(2) Effect of temperature
Within ±0.5% of output span. (For 23 ℃±10℃ variations)
(3) Effect of auxiliary power supply
Within ±0.25% of output span. (For rated voltage ±10% variations)
(4) Effect of frequency
Within ±0.25% of output span. (For standard frequency ±5% variations)
(5) Effect of input voltage
Within ±0.25% of output span. (For standard vortage ±10% variations)
(6) Effect of power factor
Within ±0.5% of output span. (For 0.5-1 power factor variations)
(7) Effect of load resistance
Within ±0.05% of output span. (For load resistance range)
(8) Output ripple
Within 1%p-p of output span.
(9) Response time
Shorter than 1sec. (Time to 99% output)
(10) Dielectric strength
2000V AC,1min.(50/60Hz)
(Between input,output,auxiliary power and external case)
(11) Insulation resistance
Higher than 100MΩ at 500V megger.
(Between input,output,auxiliary power and external case)
(12) Weight
Approx.700g
CONNECTION DIAGRAM
※ Only 19~31V power supply specification has polarity.
DESIGNATION ITEM AT ORDER
1. TYPE AND AUXILIARY POWER SUPPLY | 2. INPUT | 3. OUTPUT | |
---|---|---|---|
EGM—□□A | —□ | —□ |
ORDER EXAMPLE
① EGM-43A-21-8
② EGM-43A-99-9 INPUT : 0~120W,110V,5A, OUTPUT : DC 0~7.5V
※With the input code as 99,indicate the primary input,and VT ratio and CT ratio,if VT and CT are used in
combination and order is made with the primary input side.In such cases the primary input,and VT ratio and CT
ratio are entered on the label.
※For special specification above contact a company representative