Fushiman RPF13 type lift type safety relief valve

Manufacturer:  Fushiman Co.,LTD.
Model: RPF13

ModelNominal diameterFluidSet pressureMaximum operating temperatureBody MaterialConnection
RPF1315〜40Steam/Gas/Liquid0.02 to 1.6 MPa220℃S.C.S.Screw in

Features

  • This safety relief valve is made entirely of stainless steel, including the spring protection tube, providing excellent corrosion resistance and durability.
  • Other characteristics are the same as ductile iron 16K.

Specifications and Materials

ShapeSealed Type without Lever
FluidSteam, GasCold Water
PressureSet 0.02–2.0 MPa (Back Pressure: Atmospheric Pressure)
Operating Temperature一 15 to 200°C (*1)
MaterialsValve BodyStainless Steel Cast Steel
Valve SeatStainless Steel (*2)Stainless Steel, Stellite Welded
Valve DiscStainless Steel (*2)Stainless Steel, Stellite Welded
Valve StemStainless Steel
Spring Protection TubeStainless Steel Cast Steel
Adjustment SpringStainless Steel
CoverStainless Steel Cast Steel
Adjustment Screw RingStainless Steel or Stainless Steel Cast Steel
ApplicationHeaders, downstream of pressure reducing valves, thermal relief, and other piping protection
Applicable StandardsPressure Vessel Structural Standards

Note: (*1) The lower limit of the operating temperature can be manufactured up to -30°C.
(*2) Valve disc and valve seat can also be manufactured with Stellite welding.

Valve Specifications

Nominal Diameter (Inlet × Outlet)Face-to-Face DistanceHeight (H₂)Pipe ConnectionMass (kg)
LH₁InletOutlet
15 × 1541.548143.5JIS Rc ThreadedJIS Rc Threaded2.8
20 × 2041.548143.5JIS Rc ThreadedJIS Rc Threaded3.0
25 × 2545.556163JIS Rc ThreadedJIS Rc Threaded3.9
32 × 3252.570187.5JIS Rc ThreadedJIS Rc Threaded6.5
40 × 4057.575215JIS Rc ThreadedJIS Rc Threaded8.7

RPF12 Type・RPF13 Type Saturated Steam Discharge Capacity (According to Pressure Vessel Structure Regulations)

Nominal Diameter15-20253240506580
Seat Bore Diameter D (mm)21263341516681
Lift l (mm)0.60.70.91.11.31.72.1
Blowout Area A (mm²)/Set Pressure (MPa·G)Coefficient CSet Pressure (MPa·G)39.557.193.3141.6208.2352.4534.3
0.11.000405895144212359544
0.21.0005884138209308522791
0.31.000781131852824147011064
0.41.003991432343555228841340
0.50.99911817128042562610591606
0.60.99513819932649572912341871
0.70.99115722837256583114072133
0.80.98717625541763493215782393
0.90.985196283463704103517522656
1.00.983215311509773113719252919
1.10.980234339554841123720953177
1.20.978254367600910133922663436
1.30.976273394645979143924373695
1.40.9752924226901048154126093957
1.50.9743114507361117164327824218
1.60.9733314787821186174529534478
1.70.9723505068271255184631254738
1.80.9713695348721324194732964998
1.90.9703885619171393204834675257
2.00.9704085909641463215136415521

RPF12 Type・RPF13 Type・RPS16 Type・RPS17 Type Air Discharge Capacity (According to Pressure Vessel Structure Regulations, at 20°C)

Nominal Diameter15-20253240506580
Seat Bore Diameter D (mm)21263341516681
Lift l (mm)0.60.70.91.11.31.72.1
Blowout Area A (mm²)/Set Pressure (MPa·G)39.557.193.3141.6208.2352.4534.3
0.16594153233343581881
0.2941372233394998451282
0.312718430045667111361723
0.415923137757384314272163
0.5192278454690101417172604
0.6225325531807118620083045
0.7257372608923135822993486
0.82904196851040153025903926
0.93224667621157170128804367
1.03555138391274187331714808
1.13885609161391204534625249
1.24206089931507221737525690
1.345365510701624238840436130
1.448570211471741256043346571
1.551874912241858273246257012
1.655079613011975290449157453
1.758384313782092307652067893
1.861689014552208324754978334
1.964893715322325341957878775
2.068198416092442359160789216

RPF12 Type・RPF13 Type・RPS16 Type・RPS17 Type Air Discharge Capacity (According to High-Pressure Gas Safety Act, at 20°C)

Nominal Diameter15-20253240506580
Seat Bore Diameter D (mm)21263341516681
Lift l (mm)0.60.70.91.11.31.72.1
Set Pressure (MPa·G)/Blowout Area A (mm²)0.3950.5710.9331.4162.0823.5245.343
0.16189145221324550833
0.2931352213364958381270
0.312618229845266511261707
0.415822937456883514142144
0.5190275450684100517022581
0.6223322527799117619903018
0.7255369603915134622783454
0.82874156791031151625663891
0.93204627551147168628544328
1.03525098321262185631434765
1.13845559081378202734315202
1.24166029841494219737195639
1.344964910601610236740076075
1.448169611371726253742956512
1.551374212131841270845836949
1.654678912891957287848717386
1.757883613662073304851597823
1.861088214422189321854478260
1.964292915182304338857368696
2.067597615942420355960249133

RPF12 Type・RPF13 Type Water Discharge Capacity (According to General Discharge Capacity Calculation Formula)

Nominal Diameter15-20253240506580
Seat Bore Diameter D (mm)21263341516681
Lift l (mm)0.60.70.91.11.31.72.1
Set Pressure (MPa·G)/Blowout Area A (mm²)39.557.193.3141.6208.2352.4534.3
0.1134919503186483671101203518248
0.21907275745066839100561702025806
0.32336337755198376123162084631606
0.42698390063729672142212407136496
0.530164360712510813159002691240803
0.633044776780511845174172948144698
0.735695159843012795188133184348279
0.838155515901213678201123404151613
0.940475850955914508213323610654744
1.0426661661007615293224863805957705
1.1447464671056816039235833991760522
1.2467367551103816752246324169263213
1.3486470311148917436256384339565794
1.4504772961192218095266054503368278
1.5522475521234118730275394661370674
1.6539678001274519344284424814272992
1.7556280401313819939293184962475238
1.8572382731351920517301685106277420
1.9588085001388921080309945246179541
2.0603387211425021627318005382481607

Notes:

  1. The discharge capacity calculation formula is based on the vent well calculation formula in the High-Pressure Gas Safety Act.
  2. This table applies to cases where the back pressure of the discharge outlet is atmospheric pressure and the overpressure is 25%.
  3. If G ≠ 1, multiply the values in the table by the G value to obtain the required discharge capacity.