Fushiman P100-2F Pressure Reducing Valves

Manufacturer:  Fushiman Co.,LTD.
Model: P100-2F

P100-2F Type Pressure Reducing Valve

ModelNominal DiameterInlet PressureSecondary Measurement RangeMaximum Operating TemperatureBody MaterialConnection
P100-2F40・50MAX. 2.0MPa0.2~0.7MPaRoom temperature (20°C)CACThreaded connection

(Foundation) Japan Fire Equipment Safety Center Registered Certified Product
Certification Number: VA-038-1

Applicable Locations and Functions

● Reduces the pressure inside the piping to a constant level. (Secondary pressure regulating valve)
● Can be used for firefighting equipment, mainly indoor fire hydrant systems.

Specifications and Materials

Nominal Diameter4050
Maximum Primary Side Operating Pressure2.0 MPa
Set Pressure Adjustment Range0.2–0.7 MPa
TemperatureRoom temperature (20℃)
Rated Cv Value8.313
Maximum Flow Rate250 L/min400 L/min
Minimum Differential Pressure Required for Maximum Flow0.44 MPa or higher0.46 MPa or higher
Offset0.15 MPa or less
Shut-off Pressure Rise0.05 MPa or less
Minimum Set Differential Pressure0.05 MPa
Flow Rate at Minimum Set Differential Pressure (ΔP = 0.05 MPa)84.6 L/min
Minimum Differential Pressure Required for 130 L/min0.12 MPa or higher0.05 MPa or higher
Minimum Adjustable Flow Rate2.6 L/min
Value When Valve Fully Open10 ±10%17 ±10%
Pressure Reducing Mechanism (Type of Pressure Reducing Valve)Direct Acting Type
Main Component Material (Valve Body)AC2A (Aluminum Alloy)
Weight5.5 kg8 kg

Note (1) △P is the differential pressure between the primary side pressure P₁ and the secondary side pressure P₂

Dimensions

Nominal DiameterdLH1H2E
4017040243130
5019548292145

Performance Diagram

● Flow Rate vs. Differential Pressure Diagram at Full-Open Pressure Reducing Valve

REQUEST QUOTATION

PAYMENT

payment-methods

Return Top