Fushiman P260-1LFA Remote Adjusted Pressure Reducing Valves

Manufacturer:  Fushiman Co.,LTD.
Model: P260-1LFA

ModelNominal Diameter
Primary
Side
Pressure
Secondary
Side Set
Range
Maximum Operating TemperatureBody MaterialConnection
P260-1LFA15〜80MAX. 1.0MPa0.03~0.9MPa220℃FC,FCDFlange
  • Simply connecting an operational air pressure regulator allows for remote setting of the desired pressure.
  • By setting the operational air pressure to zero, the line can be remotely shut off.
  • Exceptional performance as a pressure-reducing valve.
  • Suitable for explosive atmospheres.
  • Compact and lightweight.
  • Can be converted to a remote-setting type by replacing a few components, even for an in-use P260 model.

Specifications and Performance

Nominal Diameter15–80 (1)
FluidSteam
Primary Side SteamMaximum Pressure1.0 MPa (2)
Maximum Temperature220°C
Secondary Side Pressure Setting Range0.03–0.9 MPa
Operating Air PressureSet Pressure + 0.05 MPa (3)
Cv Value (4)4.5d² ~ 3.1d²
Maximum Pressure Reduction Ratio20:1
Minimum Setting Differential Pressure10% of Primary Side Pressure (Minimum Value 0.07 MPa)
Offset0.03 MPa or less
Shutoff Pressure Rise0.02 MPa or less
Minimum Adjustable Flow Rate5% of Rated Flow
Seat Leakage Rate0.05% or less of Rated Flow
Main MaterialsValve BodyCast Iron (5)
Main Valve & SeatStainless Steel
Piston & CylinderStainless Steel
DiaphragmStainless Steel
Pipe ConnectionJIS 10K Full-Face Flange

Notes:

  1. We also manufacture nominal diameters 100 to 150.
  2. We also manufacture products with a primary-side pressure exceeding 1.0 MPa.
  3. We also manufacture products with a setting pressure / operating air pressure ratio of 2.
  4. The Cv value is the same as the P260 type pressure reducing valve.
  5. The valve body for nominal diameters 15 to 40 is made of ductile cast iron.

Structure and Dimensions

Nominal DiameterL (mm)Hi (mm)h2 (mm)K (mm)Weight (kg)
15145811711168
20150761761168.5
251607317811610
321757718811612
401908519811214
502109521211218
6523511123111226
8026512324811232

The selection of nominal diameters, piping examples, and alarm safety relief valves is the same as for the P260 type pressure reducing valve.

REQUEST QUOTATION

PAYMENT

payment-methods