Fushiman PFD42 Pressure Reducing Valves

Manufacturer:  Fushiman Co.,LTD.
Model: PFD42

PFD42 Type Pressure Reducing Valve

ModelNominal DiameterInlet PressureSecondary Pressure RangeMax Operating TemperatureBody MaterialConnection
PFD4240〜150MAX. 1.6MPa0.05~1.2MPa90℃FC,FCDFlange

(Foundation) Japan Fire Equipment Safety Center Registered Certified Product
Certification Number: VA-035

Applicable Applications and Functions

Reduces pipeline pressure to a constant level (Secondary pressure adjusting valve)
Applicable for:

  • Indoor fire hydrant systems
  • Sprinkler systems
  • Water mist fire suppression systems
  • Foam fire suppression systems
  • Outdoor fire hydrant systems
  • Water transmission piping systems

Specifications

Nominal Diameter40506580100125150
Maximum Operating Pressure (Primary Side)1.6MPa
Set Pressure Adjustment Range0.05–0.4, 0.4–1.2MPa
Pressure Difference Between Primary and Secondary Side0.04–1.55MPa
Operating TemperatureMAX. 90℃
Rated Cv Value22.5406390160250360
Maximum Flow Rate (ℓ/min)53380013002000300050007700
Offset0.08MPa or less
Minimum Differential Pressure0.04MPa
Minimum Adjustable Flow Rate10 ℓ/min60 ℓ/min
Shutoff Pressure Rise0.08MPa or less
Fully Open Cv Value255079145190325473
Pressure Characteristics VariationLess than 0.02MPa per 0.1MPa primary side pressure change
Pressure Adjustment Mechanism (Type of Pressure-Reducing Valve)Pilot Operated
Main Component Material (Main Valve Body)FCD450FC200
Installation ConditionsUpright on horizontal piping or sideways on vertical piping

Dimensions and Weight

(mm, kg)

Nominal Diameter40506580100125150
Valve Body: Cast Iron JIS16KL220260290334394474534
H1759097110125155175
H2247268268268268298332
A130142153163193214231
E8793105125147177207
Mass (kg)162032396294138

 

REQUEST QUOTATION

PAYMENT

payment-methods

Return Top