Fushiman RPC14 relief valve

Manufacturer:  Fushiman Co.,LTD.
Model: RPC14

ModelNominal diameterfluidSet pressureMaximum operating temperatureBody MaterialConnection
RPC1415〜80Liquid0.04 to 1.6 MPa200℃FCFflange

Features

 RPC14 type ・ Cast iron ・ 16K ・ Same as the screw-in shape.

ShapeLeverless Sealed Type
FluidWater, Oil, Non-Corrosive Liquids
PressureSet Pressure: 0.04–16 MPa (Back Pressure: 1.0 MPa or less)
Operating Temperature0–200°C
Maximum Usable Viscosity2000 mm²/s (At Operating Temperature)
MaterialValve BoxCast Iron (15A–40A JIS 16K is Ductile Cast Iron)
Valve SeatStainless Steel
Valve BodyStainless Steel
Valve StemStainless Steel
Spring Protection TubeCast Iron
Adjustment SpringSpring Steel, Piano Wire
LidCast Iron
Adjustment ScrewBrass
ApplicationPump Bypass, Back Pressure Valve
Applicable StandardsPressure Vessel Structural Standards

Note (1): We will also consider cases where the viscosity exceeds 2000 mm²/s.

  • If there is pressure (back pressure) on the outlet side, the blow-off pressure will differ from the set pressure of the valve.
    Additionally, if the back pressure changes, the blow-off pressure will also change.
    When there is back pressure, the inlet pressure will be the set pressure plus the back pressure. The maximum inlet pressure is the same as the nominal flange pressure.

Dimensions and Mass

Nominal Diameter (Inlet × Outlet)Face-to-Face DimensionsHeight (H₂)Pipe ConnectionWeight
LHiInletOutlet
15X 157368136JIS10K 全面座JIS10K 全面座3.8
20 x 2075701364.2
25 x 2585851486.5
32 x 3295901729.2
40 x 401009519110.8
50 x 5011010523815.6
65 x 6513012028625.7
80 x 8014013534333.2
15X 207583143JIS 16K 全面座JIS10K 全面座4.7
20 x 2575851435.4
25 x 3290901587.5
32 x 40959518310
40 x 5010010520613
50 x 6511511525017.2
65 x 8013013030326.5
80X10014514535838

RPC14 Model Water Discharge Volume (Based on General Discharge Volume Calculation Formula)

Nominal Diameter1520253240506580
Seat Bore Diameter D (mm)2020253240506580
Lift l (mm)0.280.50.630.81.01.251.632.0
Set Pressure (MPa·G)/ Blowout Area A (mm²)12.422.234.956.888.8138.8235.3355.3
0.14237581191193930324740803612134
0.2598107216852743428967041136417160
0.3733131320643360525282101391921017
0.4847151623833879606594801607224269
0.59461695266543376781106001796927133
0.610371857291947517428116111968429723
0.711202006315351328024125422126132105
0.811972144337154868578134082272934321
0.912702274357558199098142212410836403
1.013392397376961349590149902541238373
1.1140425143953643310058157222665340246
1.2146726264129672010505164212783842035
1.3152627334297699410934170922897543752
1.4158428364459725811347177373006845403
1.5164029364616751311746183593112446997
1.6169430324767775912131189613214548538
1.7174631264914799812504195453313450032
1.8179632165057823012867201123409451482
1.9184533045195845513219206633502952893
2.0189333905330867513563212003593954267
  1. The discharge volume calculation formula is based on the calculation formula for relief valves in the High-Pressure Gas Safety Act.
  2. This table applies when the valve outlet pressure is atmospheric pressure and the overpressure is 25%.
  3. If G ≠ 1, multiply the values in the table by the corresponding G value to obtain the required discharge volume.

R101-1BHA Model Water Discharge Volume (Based on General Discharge Volume Calculation Formula)

Nominal Diameter15-20253240
Seat Bore Diameter D (mm)20253240
Lift l (mm)0.70.81.01.3
Set Pressure (MPa·G)/ Blowout Area A (mm²)43.962.8100.5163.3
0.11499214434325645
0.22120303348547983
0.32596371459459778
0.429984289686411291
0.533524795767512623
0.636725253840713828
0.739665674908114936
0.842406066970815967
0.9449764341029716936
1.0474167821085417852
1.1497271131138318724
1.2519374291189019556
1.3540577331237520355
1.4560980251284221123
1.5580683061329321865
1.6599785791372922582
  1. The discharge volume calculation formula is based on the calculation formula for relief valves in the High-Pressure Gas Safety Act.
  2. This table applies when the valve outlet pressure is atmospheric pressure and the overpressure is 25%.
  3. If G ≠ 1, multiply the values in the table by the corresponding G value to obtain the required discharge volume.