Japan, Krohne
Krohne OPTIWAVE 1520 Radar (FMCW) Level Transmitter
![](https://koueitrading.com/global/wp-content/uploads/2020/06/Screenshot_2024-06-20_101254-removebg-preview-575x380.png)
Made in Japan
Manufacturer: KROHNE Japan KK
Model: OPTIWAVE 1520
Features
- Very economical level solution for simple applications with moderate accuracy requirements (±5 mm / ±0.2 in)
- Robust PVDF housing (IP68): Level transmitter withstands heavy rainfall and flooding events for several days
- PVDF Lens antenna in DN40 / 1½”
- Virtually no dead zone
- Small beam angle of 8° for reliable level measurement in narrow tanks and basins
- Antenna material is chemically resistant to a wide range of products
- Extremely high dynamics for reliable level measurement also in the event of condensation or agitated surfaces
- TBM (Tank Bottom Management) ensures reliable measurement even in empty tanks
- Dedicated algorithms to filter and compensate for irregular radar wave reflections that occur at tank bottom when the vessel is empty
- Allows for quick and easy commissioning of tanks regardless of their size, material or geometry
- User-friendly device installation and set-up, easy commissioning possible without prior knowledge
- Via Bluetooth® in combination with mobile phone or tablet and the OPTICHECK Level Mobile
- Via HART® using the OPTICHECK DTM with quick set-up assistant
- Features OPTICHECK technology built-in
- Enhanced device diagnostics
- On-site verification without process interruption using the OPTICHECK service tools
- Verification report about device status with one click
- Delivered with a 5 m / 16.4 ft shielded cable
- Large choice of accessories available – from orientation kits to brackets and low pressure flanges to weather protections and purging kits
Typical Applications
General
Basic applications with open or pressurised tanks and moderate accuracy requirements
Level monitoring in harsh outdoor environments
Level measurement of solids, e.g. bulk solids in silos
Water and wastewater industry
Level measurement of sewage, sewage sludge, treated water, etc.
Monitoring in pumping stations, sewage screw lifting stations, rain water basins, etc.
Measurement of sand, gravel or waste from coarse and fine screens (rags, debris, etc.)
Specifications
General Information | |
---|---|
Product type | Level transmitter |
Product family name | OPTIWAVE |
Product positioning | For basic liquid applications |
Product variants | OPTIWAVE 1520 – IP68 rated, without display |
Measurement variables | Distance, Level, Reflection, Volume |
Measurement principle | Radar |
Level measurement type | Continuous measurement |
Contact to measured medium | No |
Interface measurement | No |
Redundancy | No |
Measured media | Liquids |
Measuring range (liquids) | 0…10 m / 0…32.8 ft |
Ambient temperature | -25…+80°C / -13…+176°F |
Measuring point | Pressurised tank, Open tank, Open basin, Shaft |
Operating conditions | |
Process pressure | -1…5 bar / -14.5…72.5 psi |
Process temperature | -25…+80°C / -13…+176°F |
Materials | |
Antenna | Polyvinylidene fluoride (PVDF) |
Gaskets | Ethylene propylene diene monomer (EPDM) |
Wetted parts | Polyvinylidene fluoride (PVDF), Ethylene propylene diene monomer (EPDM) |
Process connections | |
Thread connections | Male: G1½, 1½ NPT |
Approvals/Standards | |
Ingress protection | IP66/68 |
Communication | |
Analogue outputs | 4…20 mA |
Digital outputs | HART®, Bluetooth |
Accuracy | |
Accuracy (liquids) | Max. measuring error: ±5 mm / ±0.2″ Repeatability: ±1 mm / ±0.04″ |
Related Products
-
Kyowa PVL-200KB PVL Voltage-output Pressure Transducer
-
Yamayo FC, OC, OCB Metric (JIS) Convex Pocket Steel Measuring Tape
-
Kakuta No.AC450 Air Clamp
-
Tsugaru Kogyo No.8542 (orthogonal) / 8543 (free) 40 Square x Versatile Clamp (Orthogonal & Swivel)
-
Ascon BAR-T type (direct pressure type) intermittent mechanism Indexing table automatic machine Blast Cabinet
-
Watanabe FD1-F Wind Speed Detector Duct Insertion Type (with temperature compensation)