Miyawaki
Miyawaki CTC-P Two-Bolt Connectors
Manufacture: MIYAWAKI Inc.
Model: CTC-P
Features
Quick maintenance and replacement of steam traps with two-bolts connector
Multifunctions
Multifunctions with isolation valve (piston type) and drain plug that can be set on either primary or secondary side only or both sides. Drain plug in the primary side function as blow down valve and if set on secondary side too, the secondary side will function as a test valve.
Easy installation
Composition of piston valve (PVU1) and the UNC to build composite trap connector makes the possible flexible angular connection of PVU1 to UNC which enables fit-to-assembly design and easier installation in the manifold package.
Horizontal/Vertical installation
Built-in screen for safer scale removal
Typical applications
Condensate Manifold Package, Steam Traps with two-bolts pipe lines
Dimensions/Weight
PVU1
Size | Dimensions(mm) | Dimensions(in.) | Weight | |||||||||||||||
C | D | S | D1 | t | L | H1 | H2 | C | D | S | D1 | t | L | H1 | H2 | kg | lb | |
3/4×1/2 | 38 | 27,2 | 15 | 21,34 | 2,77 | 90 | 112 | 32 | 1.5 | 1.1 | 0.6 | 0.8 | 0.1 | 3.5 | 4.4 | 1.3 | 1,3 | 2.9 |
CTC-P1
Size | Dimensions(mm) | Dimensions(in.) | Weight | |||||||||||||||||
C | D | S | C1 | D1 | S1 | L | H1 | H2 | C | D | S | C1 | D1 | S1 | L | H1 | H2 | kg | lb | |
3/4×1/2 | 38 | 27,2 | 15 | 36 | 21,8 | 15 | 157 | 112 | 73 | 1.5 | 1.1 | 0.6 | 1.4 | 0.9 | 0.6 | 6.2 | 4.4 | 2.9 | 2,3 | 5.1 |
CTC-P2
Specifications
Piston Valve (PVU1) Body Material |
Universal Connector (UNC) Body Material |
Max.Allowable Pressure | Max.Allowable Temperature | Max.Operating Pressure |
Max.Operating Temperature |
||||
MPa | psig | °C | °F | MPa | psig | °C | °F | ||
A182 F304 / ASTM A105 |
CF8M / WCB | 3,2 | 464 | 400 | 752 | 3,2 | 464 | 400 | 752 |
Size | Connection | Valve Types | No. of Valves | PVU1 Seat Leakage Test | Screen |
3/4 | SW (ASME Class3000) |
Piston Valve | Primary side 1, Secondary Side 1 |
API598 (Valve Inspection and Testing) |
20 Mesh eqv. (Built-in) |
* For composite trap connector only, further restricted by mounted trap.
Cautions: To avoid injuries, this product shall be used only within the specification range.