Miyawaki RE10N Pilot Operated For Steam

Manufacturer: Miyawaki Inc.
Model: RE10N

Features

Pressure reducing valves for steam

These are automatic valves that reduce the steam supply pressure to the certified pressure for the device in use, and keep it steady.

Pilot operated valves

The drive section detects the pressure supplied from the pilot chamber, and the degree of opening of the valve is adjusted to keep the pressure on the secondary side at a set level.

Compact and cost effective design

It has a space saving (ultra small/lightweight).
Low heat dissipation with superb energy saving properties and cost performance.

Simple pressure adjustment

Pressure adjustment can be performed by hand using a handle, with no tools required. (with lock mechanism)

Superb durability

Offers superb durability thanks to an overstress prevention mechanism.

Easy maintenance

It is easy disassembly and reassembly.

Built-in strainer

RE10N

Uses

Suitable for a wide range of uses including devices for foodstuffs, dyeing, and cleaning as well as heating equipment and air conditioning equipment.

Dimensions/Weight

SizeDimensions (mm)Dimensions (in)Weight
LL1H1H2WLL1H1H2W(kg)(lb)
1/2”160175133801006.36.95.23.13.97,115.7
3/4”7,416.3
1”1701806.77.18,518.7
1 1/4”2002101541031307.98.36.14.15.114,231.3
1 1/2”14,331.5
2”2202208.78.715,634.4

Specifications

ModelConnectionMax. operating pressureOperating pressure rangeControl pressure rangeValuesMax. pressure reduction ratioMax. operating temperatureBody material
TypeSize(MPa)(psig)Primary side pressure (MPa)Primary side pressure (psig)Secondary side pressure (MPa)Secondary side pressure (psig)CvKvs(℃)(℉)
RE10NFlanged
FF,RF*
1/2”1,62320,1 – 1,614.5 – 2300,034 – 1,24.9 – 1741,00,920:1220428Ductile cast iron

FCD450

3/4”2,52,2
1”4,03,4
1 1/4”6,55,6
1 1/2”9,07,7
2”16,013,8

*Can potentially meet these flange standards: JIS 10K, 16K, 20K

Offset: up to 0,03MPa (4.4psig)
Minimum differential pressure: 0,07MPa (10.2psig)
Minimum adjustable flow rate: 5% of the rated flow rate
Lockup pressure: 0,03MPa (4.4psig) or lower

Capacity Chart

How to use selection chart (example)
To reduce the pressure of 800kg/h (1764lb/h) of steam from 0,8MPa to 0,5MPa (116psig to 73psig)

1. Find the point at which the primary side pressure 0,8MPa (116psig) curve and secondary side pressure 0,5MPa (73psig) horizontal line intersect.
2. Trace a vertical line from the point where they intersect, and look for the smallest-sized product where the steam flow rate is 800kg/h (1764lb/h) or more at the point where the vertical line you have traced intersects the horizontal size lines.
3. In this case, the pressure reducing valve with a size of 1 1/2” is optimum.

Installation Examples

Related Products Models for reference
Sight glass TS1 T3    T3
Y strainer YSF
Separator   H3  H5
Steam trap Differs depending on conditions

REQUEST QUOTATION

PAYMENT

payment-methods

Return Top