Multi MIS-A 3 Range Isolation Ohmeter (4 Analog Models)

Manufacturer: Multi Measuring Instruments Co., Ltd.
Model: MIS-A 3

Features

・Easy-to-read scale
scale ・Can be read even in dark places by phosphorescent scale plate
・With load discharge function
・Convenient structural design that allows the lid to be stored at the bottom of the main unit
・Compliant with JIS C 1302 (1994)

Body specifications

Rated voltageMS-1AMS-2AMS-3AMS-4A
50V/125V/250V125V/250V/500V125V/250V/1000V250V/500V/1000V
Voltage measurementAC0-600VAC0-600VAC0-600VAC0-600V
Accuracy±2.5%F.S±2.5%F.S±2.5%F.S±2.5%F.S
PowerAA Manganese Batteries×6AA Manganese Batteries×6AA Manganese Batteries×6AA Manganese Batteries×6
Dimensions and MassW170×H54×D105mm Approx. 350gW170×H54×D105mm Approx. 350gW170×H54×D105mm Approx. 350gW170×H54×D105mm Approx. 350g
AccessoryBattery, cord sets (line cord, ground cord, cord storage case, belt)Battery, cord sets (line cord, ground cord, cord storage case, belt)Battery, cord sets (line cord, ground cord, cord storage case, belt)Battery, cord sets (line cord, ground cord, cord storage case, belt)
OptionProbe with switch (cord length approx. 1m) (MP-001) ¥3,200 (excluding tax)Probe with switch (cord length approx. 1m) (MP-001) ¥3,200 (excluding tax)Probe with switch (cord length approx. 1m) (MP-001) ¥3,200 (excluding tax)Probe with switch (cord length approx. 1m) (MP-001) ¥3,200 (excluding tax)

 

Measurment Specifications

Rated voltage50V125V250V
Maximum effective display value10MΩ20MΩ50MΩ
Median display0.2MΩ0.5MΩ1MΩ
1st effective measurement range0.01MΩ~5MΩ0.02MΩ~10MΩ0.05MΩ~20MΩ
2nd effective measurement range0.005MΩ~0.01MΩ
5MΩ~10MΩ
0.01MΩ~0.02MΩ
10MΩ~20MΩ
0.02MΩ~0.05MΩ
20MΩ~50MΩ
Tolerance1st effective measurement range ±5%rdg
2nd effective measurement range ±10%rdg Outside
the above range ±30%rdg
Rated voltage500V1000V
Maximum effective display value100MΩ2000MΩ
Median display2MΩ50MΩ
1st effective measurement range0.1MΩ~50MΩ2MΩ~1000MΩ
2nd effective measurement range0.05MΩ~0.1MΩ
50MΩ~100MΩ
1MΩ~2MΩ
1000MΩ~2000MΩ
Tolerance1st effective measurement range ±5%rdg
2nd effective measurement range ±10%rdg Outside
the above range ±30%rdg