Nippon Flow Cell PF Series Pitot Tube Flow Meter

Made in Japan
Manufacturer: Nippon Flow Cell
Model: PF

This flow meter actively manages the flow in air conditioning systems, measuring the flow of chilled and hot water used in building air conditioning systems. Since it utilizes a Pitot tube, it is easy to install and has almost no pressure loss.

Detachable Indicator Type

PFNS-M Type [Indicator Section Made of Bronze]
PFNS-A Type [Pitot Section Made of Brass]

PFNC-M Type [Indicator Section Made of Bronze]
PFNC-A Type [Pitot Section Made of Bronze]
Fixed Indicator Type
PFT-S Type [Made of Brass]
PFT-C Type [Made of Bronze]

Features

  • Accurate measurement with a double scale.
  • Red for Hot water (60°C), Blue for Cold water (7°C).
  • The specially structured Pitot tube enables high-accuracy measurements, even with minimal straight pipe lengths of 5D upstream and 3D downstream from the installation point.
  • Maintenance and inspection of the indicator section can be done without stopping the flow.
  • Can be easily installed on existing piping.
  • Detachable indicators can be used on multiple piping systems.

Specifications

  • Accuracy: ±5.0% FS
  • Nominal Diameter: 20A to 450A (based on SGP pipe internal diameter)
  • Flow Range:
    • Water: 8 to 25,000 L/min
    • Large flow type (15 to 36,000 L/min) is also available.
  • Maximum Operating Pressure:
    • Detachable type: 1.0 MPa, 2.0 MPa
    • Fixed type: 1.0 MPa, 2.0 MPa
  • Maximum Operating Temperature: 90°C
  • Pressure Loss: Extremely small (negligible).

REQUEST QUOTATION

PAYMENT

payment-methods

Return Top