Japan, NOHMI BOSAI
NOHMI BOSAI FAP230N-1L Fire Alarm Panel
Made in Japan
Manufacturer: NOHMI BOSAI
Model: FAP230N-1L
Features
- Conventional type
- Alarm Verification type (Alarm verification time: 60 seconds)
- Various test functions: fire indication test, auxiliary power supply test and alarm verification time test.
- Durable LED indicators
- Back-up power supply (Ni-Cd battery, 24VDC)
- Easy maintenance
- Automatic self-checking system
Description
On receiving a fire signal from a fire detector or a manual alarm box, the FAP 230N-1L conventional fire alarm panel gives a visual alarm, as well as an audible alarm, to alert the alarm panel operator. It also produces alarms to alert the occupants of the building premises.
Specification
Model No. | FAP230N-1L |
Type | Wall mounting type |
Power Supply | 220VAC 50/60Hz |
Aux. Power Supply | Sealed Ni-Cd battery 0.1Ah |
Circuit Voltage | 24VDC |
Alarm Verification Time | Thermal detector 10sec., Smoke detector 60sec. |
Power Consumption | Max. approx.: 9VA (In normal condition) Max. approx.: 10VA (In alarming condition) |
Max. Permissible | Smoke detectors: Up to 30 |
Number of Apparatus | Local alarm bells: Up to 4 (For bell of 24VDC, 10mA) |
To be Connected | Indicator LED: Up to 3 (For 24V, 21mA Light Emitting Diode) |
Ambient Temperature | 0 to 40°C, 20 to 85% (RH) |
Resistance of One Detector Line | less than 50 Ω/Loop |
End-of-Line Resistor | 10kΩ 1/2W |
Weight | Approx. 1440g |
Typical wiring diagram
Dimension (wall mounting type, FAP230N-1L)
- AC POWER-ON LAMP
- AUXILIARY POWER LAMP
- FIRE ALARM LAMP
- LINE FAULT LAMP
- ALARM VERIFICATION LAMP
- ALARM TEST SWITCH
- AUX. POWER TEST SWITCH
- ALARM RESET SWITCH