Japan, NOHMI BOSAI
NOHMI BOSAI FAPN104N Series Fire Alarm Panel
Made in Japan
Manufacturer: NOHMI BOSAI
Model: FAPN104N Series
FEATURES
- Conventional type available for 30,40,50,60,70,80,90 and 100 fire zones
- Alarm verification type (Verification time : 60 seconds)
- Various test functions: fire indication test, alarm verification time test, battery test, automatic after-test resetting
- Self-diagnosis system
- Misoperation inhibit function
- Built-in telephone system
- Back-up power supply (Ni-Cd battery, 24VDC)
- Large fire alarm symbol for easy visual recognition
- Fire zone indication by both zone nameplates and a digital display
- History list for last 10,000 events
- 5 auxiliary LED indicators
- General fire alarm cut-off switch
- Functions programmable at site
- Arrow keys for easy database setting
- 5 programmable option switches for signal cut-off
- Built-in surge arrester for power lines
- 25 programmable dry contacts interlocked by zone alarm signals
- Serial output unit (RS485) is available as option unit
DESCRIPTION
The FAPN104N series fire alarm panel was developed to improve panel-front recognize-ability and functional operability from the viewpoint of users.
<Alarm inputs>
Conventional fire detectors and manual alarm boxes are connected to alarm receiving circuits to produce visual and audible alarms on the panel and to actuate alarm bells. The FAPN104N series fire alarm panel has a line-up of 30,40,50,60,70,80,90 and 100 alarm receiving circuits (zones). Each alarm receiving circuit has an alarm verification function.
<Auxiliary inputs>
Five system signals can be received by five auxiliary receiving circuits to be indicated by five LED indicators on the panel. These signals should be non-alarm supervisory signals such as sprinkler water tank water level indication and low-air pressure switch activation on dry-pipe sprinkler system.
<Signal outputs>
25 programmable contacts are available for signal output. A group of signals for a hydrant pump starting relay box and a group of signals for an annunciator panel are also available.
<Digital display>
The 3-digit digital indicator displays not only alarm-activated zones but also trouble signals and system event history list.
<Alarm bell activation>
There are 2 alarm bell activation modes. One actuates all alarm bells at the same time, called All Local Alarm ON. The other actuates a group of alarm bells depending on the location of a fire, called localized alarm. One pair of terminals is available for the general alarm. The programmable contacts are used for the localized alarm.
<Self-diagnosis>
The followings are monitored at all times:
- Open circuit of detector wiring
- Connection of the battery and fuse blown-out
- Circuit voltage trouble
- Fuse blowout
- Transmission fault
- Open/short alarms of local bells silencing circuit interlocked with emergency PA system
- Connection fault (speaker)
- Memory trouble
- Database trouble
- CPU error The fire alarm receiving circuits are tested once a week and the test results are recorded in the history list.
<Programming>
The following settings are programmable in database setting mode:
- Unused alarm receiving circuits do not need dummy current loads
- Alarm verification on alarm receiving circuits
- Five customizable LED indicators for auxiliary input signals
- Interlocking of 25 dry contacts for zone alarm signals
- Option switches on panel front
Specification
Model No. | FAPN104N SERIES |
Type | Conventional type |
Power Supply | 220VAC 50/60Hz |
Auxiliary Power Supply | Ni-Cd battery (24VDC, 1.2Ah (30-50L), 1.65Ah (60-100L)) |
Circuits Voltage | 5, 24, 48VDC, 24VAC |
Alarm Verification Time | Thermal detector: 10sec.; Smoke detector: 60sec. |
Power Consumption | Monitoring: approx. 40VA (30-60L), 60VA (70-100L) Alarm: approx. 100VA (30-60L), 210VA (70-100L) |
Maximum Number of Devices Supported | Spot type smoke detectors: 30/zone (max. no. of zones × 30/panel) Alarm bells : 45 (30-50L), 60 (60-100L) (24VDC, 10mA/bell) Location lamps: 14 (30V, 2W/lamp); 56 (24VDC, 15mA/lamp) |
Ambient Temperature and Humidity | 0 to 40°C, 20~85% RH |
Alarm Input Circuit Loop Resistance | Less than 50Ω/loop |
End-of-Line Resistor | 10kΩ, 1/2W |
Materials (Enclosure) | Steel sheet (t1.2 Front Panel, t1.6 Body) |
Color | Off-White (Nohmi white): approximating Munsell no. N8.7 or equivalent |
Weight | Approx. 22kg (30-40L), 24kg (50-60L), 37kg (70-100L) |
Dimensions | 700mm(H) x 530mm(W) x 125mm(D) (30-60L) |
1,000mm(H) x 530mm(W) x 160mm(D) (70-100L) |
Typical wiring diagram
Related Products
-
Chiyoda Tsusho MALE BRANCH TEE CONNECTOR
-
Ross Asia LF Series In-line manifold Dale series (base mounted valve)
-
TONE HDL312A Deep Socket Set (With Socket Holder)
-
Daiichi Keiki DILII Battery-Powered Digital Pressure Gauge
-
SAKUSAKU 4SS-12.0-R0.5 Carbide Radius End Mill 4-Flute
-
Kitz EA100/200-UTNE Type EA Electric Actuators/Class 10K Horizontal 3-way Stainless Steel Ball Valve