- Home
- Products
- NOHMI BOSAI FDNA002-R Protecview Aspirating Super-High Sensitivity Smoke Detection System
Japan, NOHMI BOSAI
NOHMI BOSAI FDNA002-R Protecview Aspirating Super-High Sensitivity Smoke Detection System
Made in Japan
Manufacturer: NOHMI BOSAI
Model: FDNA002-R
The Protecview is a UL/FM listed aspirating smoke detector. The Protecview is intended for early detection, early response, and early recovery of fires by monitoring the signs of fire with a high-precision sensor.
Features of FDNA002-R
- Smoke detection covers a wide range of sensitivities, from super-high to low levels (0.001 to 20%/m).
- Large flow rate fan (Maximum shutoff pressure: At least 350Pa, Maximum flow rate: At least 170ℓ/min).
- Detects smoke particles of various sizes using the Total Scattered Light Detection Principle.
- Easily monitor smoke density in real time using bar graph indicators.
- Event log function supports up to 18,000 events per detector (including detector status, smoke density trends, etc.).
- Input rated voltage: 100VAC, 24VDC.
- Stand Alone Type.
Sampling Fan
- The turbo-type large flow rate sampling fan stirs the sampled air to make it uniform, then directs part of it to the sensing chamber through the filter.
- With its powerful aspiration capacity, the fan efficiently samples and introduces air into the detector, even in strong winds and through long sampling pipes.
Filter
The filter removes dust from the sampled air, which may cause contamination in the detector and trigger false alarms, allowing the system to measure smoke density with high accuracy over an extended period.
Sensing Chamber
- Inside the sensing chamber, a laser beam irradiates the sampled air, and the light-receiving element detects the light scattered by the smoke particles.
- The Total Scattered Light Detection Principle emits the laser beam over a wide range, allowing it to detect various particle sizes, from very small (0.1μm or less) to larger ones.
- The automatic control function keeps the laser beam output constant, maintaining high sensitivity for extended periods.
- As a result, the system achieves a wide smoke detection range of 0.001 to 20%/m.
Specification of FDNA002-R
Item | Specification |
---|---|
Model No. | FDNA002-R |
Detection principle | Total Scattered Light Detection Method |
Weight | Approx. 2 kg |
Outside dimensions | W305×H235×D94.5mm |
Power supply voltage | 100VAC/24VDC, changeover |
Power/current consumption | Max. 30W (100VAC), Max. 550mA (24VDC) |
Detection range | Light obscuration rate: 0.001 – 20%/m (Alarm setting range: 0.01 – 20%/m) |
Indicator lamps | 7-LEDs (Alarm 1, 2 & 3, Power, Fault, Isolation, Audible Alarm Silence), Bar Graph Indicator, Digital Indicator |
Output signals | [Contacts signal] Contacts rating : 1A@30VDC (Fault, Alarm 1, Alarm 3) [Others] Smoke density analog output (4-20mA) |
Event log | Max. 18,000 events |
Ingress Protection Rating | IP30 |
Operation temperature and humidity | Ambient temperature for detector: -10 ~ 50°C Sampled air: -10 ~ 50°C Humidity: 95 %Rh or less (no condensation) |
System Configuration of Protecview
Related Products
-
Satuma Denki BRP2 (Disc type) AC operated DC Electromagnetic Brakes
-
UHT Corporation #200 Borazon Grinding Wheels for Spindle No.4
-
Watanabe A6000 Series A6□□6 AC Current Digital Panel Meter
-
Gentos DM Series DM-131B Flashlight (55 lumens)
-
Kanetec MTP MAGTAP
-
Murata Conductor And Conductor Band Support Fittings L-shape