NOHMI BOSAI FRRJ001-Y-4F/FRRJ001-Y-16F Initiating Device Module

Manufacturer: NOHMI BOSAI
Product name: ADDRESSABLE MODULE FOR INITIATING DEVICES (4-ADDRESS TYPE & 16-ADDRESS TYPE)
Model: FRRJ001-Y-4F/FRRJ001-Y-16F

Features of FRRJ001-Y-4F/FRRJ001-Y-16F

  • 4 & 16 consecutive addresses per unit
  • NFPA Class A (Styles 6 & 7) and Class B (Style 4) for SLC
  • NFPA Class B (Style B) for IDC
  • Electronic address setting
  • Slim unit
  • Easy installation

Description

  • The Addressable Module for Initiating Devices 4-address type and 16-address type are used to supervise the status of conventional initiating devices connected on each initiating device circuit (IDC). 4 consecutive addresses can be configured to FRRJ001-Y-4F per unit, and 16 consecutive addresses can be configured to FRRJ001-Y-16F per unit.
  • The FRRJ001-Y-4F and FRRJ001-Y-16F detect alarm conditions and report to the Fire Alarm Control Panel (FACP). The IDC wiring style is applicable to the NFPA Class B (Style B). When the FRRJ001-Y-4F or the FRRJ001-Y-16F detects an alarm, the module is latched until the system is reset.The FRRJ001-Y-4F and the FRRJ001-Y-16F are slim units, and they can be installed easily.

Specifications of FRRJ001-Y-4F/FRRJ001-Y-16F

No.ItemSpecification
1Rated voltage of SLC input power (S+, S-)24.0V
2Maximum current consumption of SLC (S+, S-)250µA
3Applicable SLC wiring styleNFPA Style 4, 6, and 7
4Operating voltage of external power supply line (PF, PF0)24.0V
5Rated output voltage of IDC (C, L)24.0V
6Maximum module standby current of IDC 24VDC (C, L)FRRJ001-Y-4F: 1.50mA, FRRJ001-Y-16F: 6.40mA
7Maximum detector standby current of IDC 24VDC (C, L)1.35mA
8Maximum module and detector alarm current of IDC 24VDC (C, L)30mA
9Applicable IDC wiring styleNFPA Style B (i.e. Class B)
10Number of addresses per unitFRRJ001-Y-4F: 4 addresses, FRRJ001-Y-16F: 16 addresses
11Maximum wiring resistance of IDC (C, L)50Ω
12Maximum wiring capacitance of IDC (C, L)1µF
13End-of-line device for IDC (C, L)Model no. FZE016A
14Operating temperature range-10°C to 50°C (14°F to 122°F)
15Operating relative humidity range20 to 85% (non-condensing)
16DimensionsFRRJ001-Y-4F: 68mm (2.68 inches) (H) x 34mm (1.34 inches) (D)
FRRJ001-Y-16F: 68mm (2.68 inches) (H) x 74mm (2.91 inches) (D)

Compatible Conventional Detectors

Series/Model NumberTypeMaximum connectable number
FDS01UIonization20 units
FDS226 seriesDitto30 units
FDS240 seriesDitto30 units
FDK01UPhotoelectric20 units
FDK101UPhotoelectric with fixed heat20 units
FDK226 seriesPhotoelectric30 units
FDK229 seriesDitto20 units
FDK246 seriesDitto30 units
FDK282 seriesDitto20 units
PSD7155DDitto (Product of Kidde-Fenwal)20 units

Installation

Figure 1: Installation in an electrical enclosureFRRJ001A-Y-S/FRRJ001-Y-4S

Wiring Diagram

Figure 2: Wiring diagram of FRRJ001-Y-4F

FRRJ001-Y-4F/FRRJ001-Y-16F