NOHMI BOSAI FRRU004-AIM Analog Input Module

Manufacturer: NOHMI BOSAI
Model: FRRU004-AIM

Features of FRRU004-AIM

  • One simple LED for status indication
  • NFPA Class A (Styles 6 & 7) and Class B (Style 4) for SLC
  • NFPA Class A (Style D) and Class B (Style B) for IDC
  • Electronic address setting
  • Downsized unit
  • Easy installation

Description

  • The FRRU004-AIM module monitors industry-standard 4–20 mA sensors.
  • This module converts sensor output into a communication protocol, enabling fire alarm control panels (FACP) to display and monitor the data.
  • It works with a wide range of sensors, including gas, temperature, and air speed sensors, all using the 4–20 mA protocol.
  • The FRRU004-AIM module features a red LED that indicates system status. When the sensor is operating normally, the LED flashes.
  • A solid LED indicates an input condition, while the LED turns off to signal a trouble condition.

Specifications of FRRU004-AIM

No.ItemSpecification
1Rated voltage range of SLC input power (S+,S-)22.0 to 24.0 V
2Maximum SLC 24 VDC standby current (S+,S-)250 µA
3Maximum SLC 24 VDC alarm current (S+,S-)250 µA
4Operating voltage of external power supply line (24+,24-)24 VDC
5Rating for connected V+,V-0.5 A
6Sensor signal loop current4-20mA
7Consumption current of the board at standby1mA
8Consumption current of the board at alarm3mA
9Maximum number of sensor per module1 unit
10Operating temperature range0 to 49°C (32 to 120°F)
11Operating humidity range0 to 93% (non-condensing)
12Address per module1 address
13Dimensions4.17”(106mm) (H) × 4.17”(106mm) (W) × 1.14”(29mm) (D)

Installation

Figure 1: Installation into the compatible electrical box

Wiring Diagram

Figure 2: Wiring diagram of FRRU004-AIM