NOHMI BOSAI
NOHMI BOSAI FRRU004-MCM Miniature Contact Module
Manufacturer: NOHMI BOSAI
Model: FRRU004-MCM
Features of FRRU004-MCM
- NFPA Class A (Styles 6 & 7) and Class B (Style 4) for SLC
- NFPA Class B (Style B) for IDC
- Electronic address setting
- Mini-sized unit
- Easy installation
Description
- The FRRU004-MCM Miniature Contact Module is a compact device designed to monitor the contact status of an initiating device that contains a normally open or normally closed contact. This module plays a crucial role in fire alarm systems by supervising the contacts and reporting their status to the Fire Alarm Control Panel (FACP).
- When the normally open contact is selected, and the contact closes, the FRRU004-MCM immediately sends a report to the FACP. Similarly, when a normally closed contact is used, and it opens, the module also updates the control panel.
- This miniature contact module supervises an open circuit linked to the C and NO (NC) terminals. Its compact design makes it ideal for use in pull stations or other fire safety devices housed in electrical boxes or enclosures.
- Additionally, the module features a UL-listed terminal block, ensuring that it meets safety standards by protecting against short circuits and ground faults. As a result, the FRRU004-MCM offers reliable performance in monitoring fire alarm systems.
Specifications of FRRU004-MCM
No. | Item | Specification |
---|---|---|
1 | Rated voltage range of SLC input power (S+, S-) | 22.0 to 24.0V |
2 | Maximum SLC 24 VDC standby current (S+, S-) | 250μA |
3 | Maximum SLC 24 VDC alarm current (S+, S-) | 250μA |
4 | IDC input circuit wiring style | Class B (Style B) |
5 | End-of-line resistor for IDC | 5.1kΩ, 1/2W |
6 | Maximum wiring resistance of IDC | 100Ω |
7 | Maximum wiring capacitance of IDC | 1μF |
8 | Operating temperature range | 0°C to 49°C (32°F to 120°F) |
9 | Operating humidity range | 0 to 93% (non-condensing) |
10 | Dimensions | 65.5mm (2.58 inches) (H) × 59mm (2.32 inches) (W) × 24mm (0.94 inch) (D) |
11 | Applicable electrical box for installation | North American 64mm (2-1/2 inches) deep single-gang box |
Wiring Diagram
Related Products
-
NOHMI BOSAI FDLU019-D-X Fixed Temperature Heat Detector
-
NOHMI BOSAI Perf-EX Inside Air High Expansion System
-
NOHMI BOSAI FRRU004-GSCU Gas Suppression Control Unit
-
NOHMI BOSAI PCA-N3060-FIM2 Fiber-optic Interface Module
-
NOHMI BOSAI N765 Addressable Systems
-
NOHMI BOSAI FQIU004-SCI Short Circuit Isolator