Japan, NOHMI BOSAI
NOHMI BOSAI PDCJ001-D Non-Explosion-Proof Type
Made in Japan
Manufacturer: NOHMI BOSAI
Model: PDCJ001-D
Descriptions of PDCJ001-D
- Nohmi’s infrared three-wavelength flame detector quickly detects fire even in places with ventilation flow, external air, or high ceilings where detection is often difficult for the ordinary detectors.
- This high-sensitivity detector is suitable not only for large spaces but also for outdoor facilities.
Features of PDCJ001-D
1. High sensitivity
Catches the flame of 33 cm² normal heptane fire tray at a distance of 60 m. (It is also possible to detect flames more than 60m away depending on the scale of the flame.)
2. Reliable fire detection
The energy intensity of the three wavelength bands in the CO₂ resonance radiation band and the flicker of the flame are judged as “fire” by an advanced algorithm to suppress false alarms.
3. Equipped with self-diagnosis function
The internal circuit is constantly checked, and if an error occurs, a trouble signal is transmitted. The contamination of the light-receiving window is also automatically checked.
Infrare Three-Wavelength Flame Detector
Type | Infrared Three-Wavelength Flame Detector |
---|---|
Model | PDCJ001-D |
Detection wavelength band | Three wavelength bands between 4.0 μm and 5.0 μm |
Detection sensitivity | 33 cm² Normal Heptane Flame Detection at 60m Front Distance |
Detection viewing angle | Horizontal and vertical 90° (The angle at which the monitoring distance is 1/2 to the front direction) |
Rated voltage | 24 VDC |
Consumption current | Monitoring & Alarming: 15 mA, Testing: 95 mA, Transmitting: 100 mA plus to the value on the above |
Delay time | Approximately 3 seconds (default), Changeable by setting |
Indicator light | Red LED |
Test function | The contamination of the light-receiving window and the operating status of the internal circuit are checked by the pseudo-fire light, and a trouble signal is transmitted in case of an abnormality |
Self-diagnosis function | The internal circuit is constantly checked, and if an error occurs, a trouble signal is transmitted. |
Power supply voltage monitoring function | When the power supply voltage drops below specified value, a trouble signal is transmitted. |
Connection cable specifications | General purpose terminals: φ0.9 ~ 1.6 shielded communication cable (Recommendation: Heat-resistant shielded cable) Transmission purpose terminals: φ0.9 shielded twisted pair cable (Recommendation: N-300-SB0.9-1P manufactured by Nippon Electric Wire & Cable Co., Ltd.) |
Environmental condition | Operating temperature: −20 to 60°C Operating humidity: 0 to less than 100% (RH), No condensation |
Main material | Aluminum alloy |
Finish | Urethane paint |
Dimensions | H118×W118×D84 (mm) |
Weight | Approximately 1.3 kg |
Dedicated control panel
Type | Dedicated control panel | ||
---|---|---|---|
Model | PAPJ002-R-CL (n:Number of zones) Without battery | PAPJ002-R-CL-P (n:Number of zones) With battery | |
Number of circuits | 4 / 8 / 12 zones | ||
Mounting type | Wall mounting, indoor use | ||
Main power supply | 100 VAC±10%, 50/60Hz | ||
Circuit voltage | 5 VDC: Microprocessor, IC, display circuit, and switching circuit 24 VDC: Others |
5 VDC: Microprocessor, IC, display circuit, and switching circuit 56 VDC: Battery charging circuit (full-wave rectification) |
|
Power consumption | 21VA (Monitoring), 100 VA (Alarm) | 100 VA (Alarm) | |
Maximum number of devices | Infrared Three-Wavelength Flame Detector: 1 unit/circuit | ||
Panel sound | Built-in electronic buzzer (Alarm, Constant, Trouble: Intermittent) | ||
Number of local alarm devices | 1 | ||
Maximum number of local alarm devices | 15 units (10mA/unit in active condition) | ||
Detector operation test | Manual operation test of the detector (by the test switch) | ||
Reset | Reset of detectors and signal-receiving circuits (by the reset switch) | ||
Signal cut-off | Cut-off of alarm and trouble output signals (by the signal cut-off switch) | ||
Alarm silence | Silence of the control panel (by the alarm silence switch) | ||
Maintenance silence | Silence of the control panel and local audible devices during the maintenance (by pressing the alarm silence switch for 5 seconds) | ||
Local alarm silence | Silence of the local audible devices (by the local alarm silence switch) | ||
Alarm verification release | Alarm verification release: Alarm notification with verification (by the alarm verification release switch) | ||
Battery test | Manual test of the battery (by the aux. power test switch) | ||
Trouble notice | Detector line open, Device fault, AC power fault, Circuit voltage fault, Fuse blow, Flame Receiving circuit fault Detector line open, Device fault, AC power fault, Circuit voltage fault, Fuse blow, Flame Receiving circuit fault, battery fault |
||
Input (terminal symbol) | Detector monitoring (C, L) | ||
Signal output | General Alarm: 2 points (Dry A contact, 24VDC/1A) Trouble: 1 point (Dry A contact, 24VDC/1A) Zone: 2 points (Dry A contact, 24VDC/1A) |
||
Environmental condition | Operating temperature: −20 to 85% (RH), No condensation | ||
Maximum cable length | 560 m (when the cable size is φ0.9), 990 m (when the cable size is φ1.2) | ||
End-of-line resistor | 10kΩ, 1/2 W (Connected to the terminal in the detector) | ||
Main material | Steel plate t1.2 | ||
Paint color | White | ||
Weight | 4L: 13 kg, 8L: 18 kg, 12L: 19 kg 6L: 18 kg, 8L: 20 kg, 12L: 21 kg |
||
Dimensions | 4L: H550×W450×D125 mm 8L: H840×W500×D145 mm |