NOHMI BOSAI
NOHMI BOSAI PNQ/ZMQ Series Noise Reduction Nozzle
Made in Japan
Manufacturer: NOHMI BOSAI
Model: PNQ/ZMQ Series
Features of PNQ/ZMQ Series
Decreases impact on HDDs caused by the gas discharge noise
Reduces discharge noise while maintaining the fire suppression performance
Easily replace existing nozzles
Noise may affect HDDs
At a convention held by the Architectural Institute of Japan on September 11, 2010, an article entitled “Study on the effects of sound environment to precision instruments”. According to this article, noise of 110 dB or larger may cause potential damage to HDDs.
Effects caused by the gas discharge noise of a fire suppression system
The article mentioned in the paragraph on the left suggests that noise such as the gas discharge noise of a fire suppression system may have a negative impact on HDDs. Furthermore, there are risks including business downtime caused by the decreased speed of HDDs, as well as loss of data.
Development of a noise reduction nozzle
To provide HDDs with protection from the sound environment, Nohmi has developed a noise reduction nozzle that reduces gas discharge noise using our exclusive technology.
Sound Pressure level
Sound pressure curve during fire supression gas discharge
Classification | Nitrogen fire suppression system | |
---|---|---|
Nozzle type | Pendant type | Sidewall type |
Nozzle flow rate* | 90 m³/min | 90 m³/min |
Sound pressure level** | 97 dB | 99 dB |
*1 The nozzle flow rate indicated above is an example. Products with different flow rates are also available.
*2 Results (maximum value) measured in front of the discharge point, 1 m away at a 45° angle.
Specification
Classification | Product specifications | |||||
---|---|---|---|---|---|---|
Pendant type | Nitrogen fire suppression system | |||||
Model number | 25PNQ | 32PNQ | 20ZM(U) | 25ZM(U) | 32ZM(U) | 40ZM(U) |
Full length x full width (mm) | 88×90 | 93×110 | 90×97 | 100×97 | 118×118 | 139×140 |
Weight (kg) | 1.2 | 2.0 | 1.4 | 1.6 | 2.2 | 3.7 |
Related Products
-
NOHMI BOSAI FDKU033-D/FDKU033-D-X Multi-criteria Analog Addresable Smoke Detector
-
NOHMI BOSAI FBMJ001/FBMJ001-D/FBMJ001-DW Fire Alarm Bell
-
NOHMI BOSAI PDCJ001-D Non-Explosion-Proof Type
-
NOHMI BOSAI CNI016N System Monitoring Program (SMP)
-
NOHMI BOSAI FDGJ Series Projected Beam Type Smoke Detector
-
NOHMI BOSAI FIRU009-R-LED LED Type Remote Annunciator