Three S Co.
Three S X Series Pneumatic: XP
Manufacturer: Three S Co., Ltd.
Model : X Series
Features
Cam action and characteristics are selectable
Value action can be switched between direct and reverse by shifting 90[deg] the position of the feedback lever A from A to B.(However the output piping has to be changed.) Also, the structure is such that the characteristics can be changed by selecting the cam. For linear motion, the standard cam can be used to select the characteristics of linear and equal %. Select any of these rotary motion, change the cam to obtain proper equal % characteristics, square-law characteristics, and equal reverse % (optional).
Model
型式 | 1 | 2 | 3 | 4 | 5a | 5b | 6 | 7 | 8 | 9 | 10 | ||
□□ | ○ | ○ | ○ | – | □ | □○ | / | □○ | □○ | □○ | □○□ | □○○ |
series | supplemental | ||||||||||
1 model |
2 series |
3 construction |
4 function &connection |
5a *1 Ambient Temp. |
5b Mounting |
||||||
1 | 100 series | 0 | standard | 1 | Rc(PT)1/4 single acting | S | standard:-20 to 83℃ | S1 | Linear motion / Side lever type | ||
XP | P/P | 2 | Rc(PT)1/4 double acting | S3 | Rotary motion / Linkage lever type | ||||||
3 | NPT 1/4 Single acting | B4 | Linear motion / Back lever type | ||||||||
4 | NPT 1/4 double acting | B7 | Concentric rotary motion / Back lever type | ||||||||
5 | Rc(PT)1/4 w/ signal transmitter | L | -50~60℃ | ||||||||
6 | NPT 1/4 w/ signal transmitter | H | 0~100℃ |
2 phase /Eq%D○○direct lever connection type w/ clump
supplemental | ||||||||||
6 *2 pressure gauge (output pressure) |
7 pilot relay / orifice |
8 input signal |
9 cam |
10 lever and clump |
||||||
M2 | 0.2Mpa | standard | C1a | linear motion / 45 4 phase linear / Eq% |
L○○ | Linear motion / Side lever type multi step lever connection type w/ clump |
||||
M4 | 0.4Mpa | cleaner | orifice dia | C3L | Rotary moton / Linkage lever type / 90 2 phase / linear |
l○○ | multi step lever connection type w/o clump | |||
M0 | 1.0Mpa | w/o | w/ | C3E | ||||||
K2 | 200kPa | F1 | Q1 | 5.0 | C3B | Rotary motion / Linkage lever ー/90 2 phase / square-law |
d○○ | direct lever connection w/o clump | ||
K4 | 400kPa | F2 | Q2 | 2.0(STD) | C3P | Rotary motion / Linkage lever type ー/90 2 phase / reverse Eq% |
K○○ | Rotary motion / Linkage lever type w/ clump | ||
K0 | 1000kPa | F4 | Q4 | 1.0 | C4La | Linear motion /45 4 phase / linear |
k○○ | Linkage connection w/o clump | ||
P2 *3 | 30psi | F5 | Q5 | 0.7 | B1 | 20~100kPa | C7L | Concentric rotary motion / Back lever type /90 2 phase / linear |
H○○ | Linear motion / Back lever type L type lever connection w/ clump |
P4 *3 | 60psi | F6 | Q6 | 0.45 | B2 | 20~60kPa | h○○ | L type lever connection w/o clump | ||
P0 *3 | 150psi | stable | B3 | 60~100kPa | V○○ | Concentric rotary motion / Back lever type Concentric rotary connection / M8 screw connection |
||||
B2 | 2bar | G1 | J1 | 5.0 | ||||||
B4 | 4bar | G2 | J2 | 2.0(STD) | ||||||
B0 | 10bar | G4 | J4 | 1.0 | ||||||
G5 | J5 | 0.7 | ||||||||
G6 | J6 | 0.45 | ||||||||
fast | ||||||||||
R1 | T1 | 5.0 |
* Model notation written in blue letters are standard model, others are option.
*1 flameproof model is S type only.
*2 please contact us for psi and bar display.
*3 No domestic sales in japan due to Non-SI unit.
Specicfication
Specs | Single acting | double acting |
Input signal (pressure) | standard: 20 to 100 kPa
(1/2 split range is available with easy adjustment) |
|
supply air pressure | 0.14~0.7MPa/140~700kPa | |
stroke / angle | Linear motion : 10~100mm
Rotary motion : 60°~90° |
|
Air connection (pressure gauge connection) | Standard: Rc 1/4(pressure gauge Rc 1/8)
Option: NPT 1/4(pressure gauge NPT 1/8) |
|
*1 pressure gauge (output pressure) |
Stadard: 0~0.2MPa、0~0.4MPa、0~1.0MPa (R) Option: kPa、psi、bar (R, NPT) |
|
Construcion | Non-explosion proof | |
Cam | Standard: Linear characteristics
Option: non-linear characteristics |
|
Ambient Temp. | Standard: (S) -20~83℃
Low temp. construction: (L) -50~60℃ High temp. construction: (H) 0~100℃ |
|
Weight | approx. 1.3kg | approx. 1.4kg |
Materials | Body: Aluminum diecastings (Special Anodize)
Cover: PBT resin(Mixed glass fiber)、Option: Aluminum diecastings (Special Anodize) |
*1 please contact us for psi and bar display
characteristics | Single acting | Double acting |
Linearity | ±1.0%F.S | ±2.0%F.S |
hysteresis | 1.0%F.S | 1.0%F.S |
repeatability | 0.3%F.S | 0.5%F.S |
sensitivity | 0.2%F.S | 0.5%F.S |
change of supply pressure | 0.2%/0.01MPa | 0.3%/0.01MPa |
orientation effect (10deg / 90deg) | 0.2% / 4.0% | |
endurance to vibration | 1%/1G | |
air consumption(Nl/min) (Nl/min) |
5.0/0.14MPa at 50% output pressure |
10/0.4MPa at 75% output pressure |
Max Cv (Nl/min) (Nl/min) |
160/0.14MPa | 370/0.4MPa |
on condition that Output is open to air (orifce dia 5mm) |
Pilot Relay | Max Cv. (Nl/min) |
Air Consumption (Nl/min) |
||||
single acting (0.14MPa) |
double acting (0.4MPa) |
|||||
XE | XP | XE | XP | |||
Standard | 160 | 370 | 5.0 | 5.0 | 10 | 10 |
Stable | 160 | 370 | 7.0 | 8.0 | 14 | 16 |
Fast | 180 | 450 | 7.0 | 8.0 | 14 | 16 |
Specifications above is effected by actuator spec
pneumatic instrument / precautions
* clean dry air (dew point – 30℃ or below) is required.
air filter (mesh 5μm or less) is required.