Japan, Toho Seisakusho
Toho Seisakusho RX-1003DK/RX-1003DKS Electric Positioner
Made in Japan
Manufacturer: Toho Seisakusho
Model: RX-1003DK/RX-1003DKS
Features
・Built-in control motor type (our first CPU-equipped type)
・(First for electric positive) By connecting a lamp etc. to the abnormality alarm output terminal, it is possible to monitor the occurrence of abnormalities from the outside.
・Added self-diagnosis function for opening input signal, feedback potentiometer input error, etc.
・You can select the stop method when an error occurs.
format | Content | Replaceable current model |
RX-1003DK | Proportional control type | RX-1003CKU/CKUI |
RX-1003DKS | Proportional control type/manual control switching type | RX-1003CKUS/CKUIS |
Specification
Power-supply voltage | AC100~AC220[V] | |||||||
Environmental response | Compliant with RoHS directive | |||||||
Vibration resistance (NEW) | IEC60068-2-6 (XYZ axis, 5-1000[Hz], 20m/S2, 90[min]) | |||||||
EMC performance | IEC61000-6-2 | |||||||
, static electricity | ||||||||
, radio frequency electromagnetic field radiation | ||||||||
, EFT/B, surge | ||||||||
, voltage dip | ||||||||
, short power outage | ||||||||
IEC61000-6-4 | ||||||||
/Conducted disturbance measurement | ||||||||
/Radiated disturbance measurement | ||||||||
Opening input signal | Current input: DC4-20[mA] | |||||||
Voltage input: DC1-5[V] | ||||||||
Voltage input: DC0-10[V] | ||||||||
input resistance | Current input: 250[Ω] | |||||||
Voltage input: 100[kΩ] or more | ||||||||
feedback potentiometer signal | 135[Ω] | |||||||
Dead zone (improved operability) | Can be set in 16 steps from 0.5 to 4.25[%] using a rotary switch (factory setting 1[%]) | |||||||
Number of steps (performance up) | Approximately 170 steps (conventional model: approximately 100 steps) | |||||||
Conditions: MCH-6CE, no load, 90 degree stroke for 30 seconds. | ||||||||
Opening output signal | Current output: DC4-20[mA] | |||||||
Voltage output: DC1-5[V] | ||||||||
Alarm output (NEW) | AC/DC24[V] 0.2[A] | |||||||
Self-diagnosis (NEW) | 4 types (opening input error, feedback potentiometer signal error, etc.) | |||||||
Restart timer (NEW) | Can be set in 10 steps from 0 to 9 [s] using a rotary switch (factory setting 0 [s]) |