Toyo Keiki ALS Series AC Current Transducer Transducer

Product Made In Japan
Manufacturer: Toyo Keiki
Model: ALS Series

ALS-0A : Fixed output load type
ALS-0CA : Regulated output current type
No assist power suppy is required.
Improved reliability and greater compactness through the use of custom ICs.
JIS c 1111 AC/DC transducer 0.5 class.

Specification

INPUT, CONSUMPTION WATTOUTPUTLOAD RESISTANCE
0~5A 50/60Hz
0~1A 50/60Hz

approx. 0.5VA

ALS-OA5 Standard types of output are availableNeed designation
Max. input
Available with range
0.1~5A
Available with frequency
range 45~10kHz
Available with
Max.voltage output 10V
Max.current output 2mA
Voltage output : above 10kΩ
Current output : below 5kΩ
Need designation
ALS-OCADC 0-1 mA 0-1 OkQ0~10kΩ(No designation)

CONNECTION DIAGRAM

SPECIFIC CHARACTER

(1) Tolerance
±0.5% of output span. (Ambient temperature 23 ℃)
(2) Effect of temperature
Within ±0.5% of output span. (For 23 ℃±10℃ variations)
(3) Effect of frequency
Within ±0.25% of output span. (For standard frequency ±5% variations)
(4) Effect of load resistance (ALS-0C type only)
Within ±0.05% of output span. (For load resistance range 0 ~10kΩ)
(5) Output ripple
Within 2%p-p of output span.
(6) Response time
Shorter than 1sec. (Time to 99% output)
(7) Dielectric strength
2000V AC,1min.(50/60Hz) (Between input,output and external case)
(8) Insulation resistance
Higher than 100MΩ at 500V megger.
(Between input,output and external case)
(9) Weight
Approx.400g

DESIGNATION ITEM AT ORDER

ALS Series

ORDER EXAMPLE
① ALS-0A-1-1-1
② ALS-0CA-1
③ ALS-0A-9-9-9 INPUT : AC0~0.5A, OUTPUT : DC 0~7.5V, LOAD : 50kΩ
※For special specifications please consult company representatives.

 

REQUEST QUOTATION