Toyo Keiki
TOYO KEIKI DEF Series Indicating Meter for Instrumentation
Product Made In Japan
Manufacturer: Toyo Keiki
Model: DEF Series
- DEF-15S (Single-pointer type)
- DEF-17S (Single-pointer type)
- DEF-15W (Two facing pointers type)
- DEF-17W (Two facing pointers type
Overview
This meter has the optimal structure and characteristics to function as an indicator for various process control systems such as power, petroleum, chemical, metal and paper plants. A state-of-the-art instrument panel receiver with an elegant, stately design and extensive functionality; this highly reliable product makes control station quality even higher.
Features DEF Series
Comparative measurements for measurement control of series such as directed standard values and measurement values can be conducted with ease because the DEF – 15W and DEF – 17W are integrated into a pair-meter structure.
Optimal for system display panels and graphic monitoring panels. Appropriate for areas with dense instrumentation as very little space is required for installation.
Characteristics
Two or more units can be neatly connected.
Tag plates are attached to the top and bottom to display information such as measuring point name and tag number.
The scale is brighter, larger, and easier to read, making it easy to perform a series of control operations.
Parts such as the zero-point adjuster and the scale plate can be replaced because the meter unit can be easily removed from the front side.
(DEF-15S & DEF-15W only)
Ordering Guide DEF Series
Models
- DEF-17S Direct-acting single-pointer (Left side only)
- DEF-15S Direct-acting single-pointer (Left side only)
- DEF-17W Direct-acting double-pointer (Two facing pointers type)
- DEF-15W Direct-acting double-pointer (Two facing pointers type)
- DEF-17S Electronic single-pointer (Left side only)
- DEF-15S Electronic single-pointer (Left side only)
- DEF-17W Electronic double-pointer (Two facing pointers type)
- DEF-15W Electronic double-pointer (Two facing pointers type)
- Input Signal
- Scale Specifications
- Coating Color
- Tag Plate Entry Characters
- Mounting Posture
Circuit System | 1) Direct-acting – Input signal is applied directly to the coil. 2) Electronic – Direct current amplification is performed for the input signal of the DC voltmeter and internal resistance is increased (DC voltmeter only). |
||
---|---|---|---|
Input Signal and | Input Signal | Input Resistance | |
DC | Direct-acting | Electronic | |
4-20 mA | 50Q±20% | ||
10~50mA | 20Q±20% | ||
1~5V | 8kO±20% | 1MQ or above | |
0-10V | 20kQ±20% | IMG or above | |
-10~0~+10 | 40kQ±20% | ||
Inputs other than those indicated above can be manufactured upon request. | |||
Tolerance | ±1% (Dependent on maximum scale value or span) | ||
Scale Length | 15 type: 100mm 17 type: 100mm | ||
Pointer | 15S: Single-pointer (Black) 15W: Two facing pointers (Black) 17 type: Lance-shaped tip knife edge, red coating is standard (Fluorescent) | ||
Scale Plate | White base, black scale, black characters | ||
Thermal Behavior | Less than 1% for 10 degrees | ||
Power Supply | Auxiliary power supply is required for electronic DC voltmeters Voltage is DC 24V±2V, approx. 20mA (per component) | ||
Influence of Variation of Auxiliary Power Supply of Electronic DC Voltmeter | Less than 0.2% for 10% | ||
Ambent Temperature and Humidity | -10°~50°, 40%~85%RH | ||
Mounting Posture | Perpendicular installation, vertical (Designate installation angles when mounting at an incline) | ||
Insulation Resistance | More than 20MQ at 500V mega (Between earth and input or power terminal) | ||
Dielectric Strength | AC 2000V for 1 minute (50/60Hz) | ||
Face Casing Coating | Standard: Black (7.5BG4/1.5 available upon request) | ||
Weight | 15S: 1. 3kg, 15D: 1.5kg, 15W: 1.5kg 17S: 0.9kg, 17 W: 1.1kg | ||
Name Plate | Affixed to the inside of the case (Material: tetrone film) | ||
Shape Dimensions | According to P3 / P4 outside dimensions. | ||
Scale Division | According to P5 scale division table. | ||
Tag Plate Entry Examples | According to P5 entry examples. | ||
Other | According to JISC 1102. |