Toyo Keiki
TOYO KEIKI GP and HP Series AC Current Transducer
Product Made In Japan
Manufacturer: Toyo Keiki
Model: GP and HP Series
AGP-□: Mean value type
AGP-□L: Mean value type, With limiter
AGP-□E: Root-mean-square value type
AGP-□EL: Root-mean-square value type, With limiter
Plug-in type makes upkeep and configuration changes simple.
Improved reliability and greater compactness through the use of custom ICs.
JIS C 1111 AC/DC transducer 0.5 class.
Specification
INPUT, CONSUMPTION WATT | OUTPUT | AUXILIARY POWER SUPPLY |
---|---|---|
0~5A 50/60Hz 0~1A 50/60Hz approx. 0.5VA |
8 standard types of output are available | AC 100/110V ±10% 50/60Hz approx. 2.5 VA AC 200/220V ±10% 50/60Hz approx. 2.5 VA DC 24V ±10% approx. 2.5 W DC 100/110V ±10% approx. 3 W |
Max. input Available with range 0.1 ~5A Available with frequency range 45Hz~10kHz |
Available with Max. voltage output 10V (600 Ω~∞) Max. current output 20mA (0 ~550Ω) |
Types are immediately available. For types not listed above contact a company representative. |
Specific Character
(1) Tolerance
±0.5% of output span. (Ambient temperature 23℃)
(2) Effect of temperature
Within ±0.5% of output span. (For 23℃±10℃ variations)
(3) Effect of auxiliary power supply
Within ±0.25% of output span. (For rated voltage ±10% variations)
(4) Effect of frequency
Within ±0.25% of output span. (For standard frequency ±5% variations)
(5) Effect of load resistance
Within ±0.05% of output span. (For load resistance range)
(6) Output ripple
Within 1%p-p of output span.
(7) Response time
Shorter than 1sec. (Time to 99% output)
(8) Effect of wave from (AGP-□E□ type only)
Within ±0.5% of output span.
(For third harmonics equivalent to 15% of the basic frequency)
(9) Dielectric strength
2000V AC,1min.(50/60Hz)
(Between input, output, auxiliary power supply and external case)
(10) Insulation resistance
Higher than 100MΩ at 500V megger.
(Between input, output, auxiliary power supply and external case)
(11) Weight
Approx.410g