Toyo Keiki
TOYO KEIKI GP and HP Series Watt Transducer
Product Made In Japan
Manufacturer: Toyo Keiki
Model: GP and HP Series
EHP-□1 : 1phase 2wire
EHP-□2 : 1phase 3wire
EHP-□3 : 3phase 3wire
Plug-in type makes upkeep and changes in configuration simple.
Improved reliability and greater compactness through the use of custom ICs.
JIS C 1111 AC/DC transducer 0.5 class.
Specification
Input
KIND | MARK | INPUT | RATED VOLTAGE | RATED CURRENT | FREQUENCY | CONSUMPTION WATT |
---|---|---|---|---|---|---|
1φ2W EHP-□1 | 1 | 0 ~ 500W | 100 V | 5A | 50/60HZ | Voltage input: 0.5VA at 1 element Current input: 0.5VA at 1 element |
2 | 0 ~ 1000W | 200V | 5A | 50/60HZ | ||
9 | OTHER | |||||
1φ3W EHP-□2 | 1 | 0 ~ 1000W | 2 X100V | 5A | 50/60HZ | |
2 | 0 – 2000W | 2 X200V | 5A | 50/60HZ | ||
9 | OTHER | |||||
3φ3W EHP-□3 | 1 | 0 ~ 1000W | 110V | 5A | 50/60HZ | |
2 | 0 – 2000W | 220V | 5A | 50/60HZ | ||
3 | 0 ~ 833W | 110V | 5A | 50/60HZ | ||
4 | 0 ~ 1667W | 220V | 5A | 50/60HZ | ||
9 | OTHER | |||||
WORKING RANGE | ||||||
Rated voltage range : 60V~240V Rated current range : 0.1A~5A Rated frequency range : 45Hz~450Hz Input range for working range 1phase 2wire : Input range ceiling 40%~120% of (rated voltage×rated current) 1phase 3wire : Input range ceiling 40%~120% of 2× (rated voltage×rated current) 3phase 3wire : Input range ceiling 40%~130% of [root3] × (rated voltage×rated current) |
OutPut
MARK | OUTPUT | LOAD RESISTANCE | WORKING RANGE |
---|---|---|---|
1 | DC 0 – 100mV | 600 Ω — ∞ | We also produce items not included in the output table on the left which cover the ranges below. Max. voltage output: 10V Loading current: below 10mA Max. current output: 20mA Loading voltage: below 11V |
2 | DC 0 – 1 V | 600 Ω — ∞ | |
3 | DC 0 – 5 V | 2kΩ – ∞ | |
4 | DC 0 – 10 V | 5kΩ – ∞ | |
5 | DC 1 – 5 V | 2kΩ – ∞ | |
6 | DC 0 – 1mA | 0 – 10kΩ | |
7 | DC 0 – 10mA | 0 – 1 kΩ | |
8 | DC 4 – 20mA | 0 – 550 Ω | |
9 | OTHER OUTPUT |
AUXILIARY POWER SUPPLY | |||
---|---|---|---|
MARK | USE RANGE | CONSUMPTION WATT | REMARK |
1 | DC 19—31V | approx. 3 W | Please inquire about items not listed on the left. |
4 | AC 80—264V (50/60Hz) DC 80-143V | approx. 4 VA approx. 3 W | |
9 | OTHER |
Specified Character
(1) Tolerance
±0.5% of output span. (Ambient temperature 23 ℃)
(2) Effect of temperature
Within ±0.5% of output span. (For 23 ℃±10℃ variations)
(3) Effect of auxiliary power supply
Within ±0.25% of output span. (For rated voltage ±10% variations)
(4) Effect of frequency
Within ±0.25% of output span. (For standard frequency ±5% variations)
(5) Effect of input voltage
Within ±0.25% of output span. (For standard vortage ±10% variations)
(6) Effect of power factor
Within ±0.5% of output span. (For 0.5-1 power factor variations)
(7) Effect of load resistance
Within ±0.05% of output span. (For load resistance range)
(8) Output ripple
Within 1%p-p of output span.
(9) Response time
Shorter than 1sec. (Time to 99% output)
(10) Dielectric strength
2000V AC,1min.(50/60Hz)
(Between input,output,auxiliary power and external case)
(11) Insulation resistance
Higher than 100MΩ at 500V megger.
(Between input,output,auxiliary power and external case)
(12) Weight
Approx.700g
Connection Diagram
※ Only 19~31V power supply specification has polarity.