Toyo Keiki NGM Series Power Factor Transducer

Product Made In Japan
Manufacturer: Toyo Keiki
Model: NGM Series

NGM-□1A : 1phase 2wire
NGM-□2A : 1phase 3wire
NGM-□3A : 3phase 3wire
Lighter because plastic is used for casing.
Improved reliability and greater compactness through the use of custom ICs.
JIS C 1111 AC/DC transducer 3.0 class.

Specification

INPUT
KIND MARK INPUT RATED VOLT. RATED CUR. FREQUENCY CONSUMPTION WATT
1φ2W NGM-□1A 01 LEAD 0.5 ~ 1 ~ LAG 0.5 100V 5A 50Hz Voltage input : 0.5VA at 1 element
Current input : 0.5VA at 1 element
Note :
1. 1 phase 2 wire and 1 phase 3 wire devices are set for a frequency of either 50Hz or 60Hz. 3 phase line devices can operate at either 50Hz or 60Hz.
2. It is necessary to balance the voltage circuits of 3 phase 3 wire devices. However, the current will behave normally if the circuits are not balanced
02 LEAD 0.5 ~ 1 ~ LAG 0.5 100V 5A 60Hz
11 LEAD 0.5 ~ 1 ~ LAG 0.5 200V 5A 50Hz
12 LEAD 0.5 ~ 1 ~ LAG 0.5 200V 5A 60Hz
99 OTHER
1φ3W NGM-□2A 01 LEAD 0.5 ~ 1 ~ LAG 0.5 2 x 100V 5A 50Hz
02 LEAD 0.5 ~ 1 ~ LAG 0.5 2 x 100V 5A 60Hz
11 LEAD 0.5 ~ 1 ~ LAG 0.5 2 x 200V 5A 50Hz
12 LEAD 0.5 ~ 1 ~ LAG 0.5 2 x 200V 5A 60Hz
99 OTHER
3φ3W NGM-□3A 21 LEAD 0.5 ~ 1 ~ LAG 0.5 110V 5A 50/60Hz
31 LEAD 0.5 ~ 1 ~ LAG 0.5 220V 5A 50/60Hz
99 OTHER
WORKING RANGE
Rated voltage range : 60V—240V
Current range : 0.1 A—5A
Frequency range : 45Hz—450Hz
Input range for working range : LEAD 0.5—1 —LAG 0.5 or LAG 0.5—1 —LEAD 0.5
OUTPUT
MARK OUTPUT LOAD RESISTANCE WORKING RANGE
1 -100 – 0 – + 100 mV 600 Ω ~ ∞ Max. voltage output: 10V, Loading current: below 10mA
Max. current output: 20mA, Loading voltage: below 11V
Relationship between input and output:
Lead side input for minus output and Lag side input for positive output are standard.
We can also make items that allow Lag side input for minus output and Lead side input for positive output.
We can also produce items that at LEAD 0.5—1—LAG 0.5 have —50%–Z+100%—F50% characteristics.
2 – 1 – 0 – + 1 V 600 Ω ~ ∞
3 – 5 – 0 – + 5 V 2k Ω ~ ∞
4 – 10 – 0 – + 10 V 5k Ω ~ ∞
5 1 – 3 – 5 V 2k Ω ~ ∞
6 1 – 0 – + 1 mA 0 ~ 10k Ω
7 – 10 – 0 – + 10 mA 0 ~ 1k Ω
8 4 – 12 – 20 mA 0 ~ 550 Ω
9 OTHER OUTPUT
AUXILIARY POWER SUPPLY
MARK USE RANGE CONSUMPTION WATT
1 DC 19V—31V approx. 3 W
4 AC 80V-264V 50/60Hz DC 80V-143V approx. 4 VA approx. 3 W
9 OTHER
0 NO ASSIST POWER SUPPLY (SELF POWER SUPPLY)

Power factor transducer may have the two types of characterristics shown below.
If no preference is specified characteristics will be as shown in 1.

NGM Series

SPECIFIC CHARACTER

(1) Tolerance
±3% of output span. (Ambient temperature 23 ℃)
(2) Effect of temperature
Within ±0.5% of output span. (For 23 ℃±10℃ variations)
(3) Effect of auxiliary power supply
Within ±0.25% of output span. (For rated voltage ±10% variations)
(4) Effect of frequency
Within ±1.5% of output span. (For standard frequency ±5%
variations)
(5) Effect of input voltage
Within ±1.5% of output span. (For standard vortage ±10%
variations)
(6) Effect of input current
Within ±3% of output span. (For 20%-120% rated current variations)
(7) Effect of load resistance
Within ±0.05% of output span. (For load resistance range)
(8) Output ripple
Within 1%p-p of output span.
(9) Response time
Shorter than 1sec. (Time to 99% output)
(10) Dielectric strength
2000V AC,1min.(50/60Hz)
(Between input, output, auxiliary power and external case)
(11) Insulation resistance
Higher than 100MΩ at 500V megger.
(Between input, output, auxiliary power and external case)

CONNECTION DIAGRAM

NGM Series

DESIGNATION ITEM AT ORDER

1. TYPE AND AUXILIARY POWER SUPPLY 2. INPUT 3. OUTPUT
NGM-□ □ A -□ -□

 

ORDER EXAMPLE
① NGM-43A-21-8
② NGM-43A-99-8 INPUT : LEAD 0.5~1~LAG 0.5,115V,5A

※Power factor measurement in circuits that have tidal currents
The effectuve measurement range of NGM type power factor transducers is LEAD 0.5~1~LAG 0.5.
Does not operate normally during backward tidal current(the current supply and receeipt flow are reversed).
To provide power factor measurements in circuits with a tidal flow the NGM-□RA type is available.

REQUEST QUOTATION

PAYMENT

payment-methods

 

TOOLS & EQUIPMENT

Lifting
Eagle Clamp | Eagle Jack | Elephant | Endo Kogyo
Japan Clamp | Kanetec | Jung | KITO | Katsuyama Kikai
Kondotec | Miki Netsuren | Sanei Seiki | Taiyo

Hand Tools
Bix | Miyakawa | Nakatani Kikai | Ogura | Osakada Tool
Super Tool | TONE | Yutani

Tape
Kamoi | Kikusui | Misuzu | Nirei | Okamoto | Taiho | Teraoka

Measurement
Hasegawa | Kawaki | Kett | KGK | Line Seiki | Nagano Keiki
Niigata Seiki | Obishi Keiki | RSK | Ryoden Shonan | Sanko
Sanwa Supply | Showa Seisakusho | Showa Sokki
SK Sato | Tokyo Keiso | Tokyo Sokushin

Safety Tools
Fujii Denko | Shigematsu | Titan

Welding
Asahi Weldex | Daihen | Koike | Nissan Tanaka

Drilling
Dijet | Kansai Kogu | Nitto Kohki | Okazaki Seiko | Takeda

Chemical
Cemedine | DaitoNippon Grease | Taseto

Other Tools
Hammer Caster | Kitagawa | Matsuda Seiki | Misuz | Sanritsu
Sanyutec | Shizuoka Seiki | Toyo Kensetsu Kohki | Yamamoto
Yamari

PLANT FACILITIES

Facilities
Acokk | Bunkaboeki | Horiuchi | Konan | Murakoshi
Murakoshi Industries | Nesstech | Nihon Flux | Nikkin Flux
NFK | Omega System | Organo | Taiyo Parker | Toyo Mic

Pump
Dynaflo | Ebara | Honda Kiko | KyowaMusashino
Tsurumi

Valve
Astam | Kyowa Iron | Nachi | Nippon Daiya | Sawada
Wasino Kiki | Yoshitake

Electricity
Arkon | Asahi Bagnal | Gentos | Iwasaki | Kokosha | U_RD

CONSTRUCTION

Concrete Work
Daia | EXEN | Japan Life | Mikasa | Okasan Kiko | Taiheiyo

Railway Work
Kyoei | Sanwa Tekki | Teikoku | Toko

Scaffolding
Bullman | Okabe | Rikiman | Tsugaru

High Tension Bolt
Dong Ah | KPF | Nippon Steel Bolten | Nippon Fastener

Bolt & Nut & Washer
Hard Lock | Kishu Fastener | Matsukin | Mori Kozai
Nakaumi | Naniwa | Ogawa | Otani | Sudo | Toneji

STEEL MATERIAL

Steel & other Material
Dongil | JIS Standard | DSR | Sumitomo Wire | Winoa IKK

Pipe
Benkan

Return Top