Toyo Keiki
Toyo Keiki TMW Series Multi Power Meter
Product Made In Japan
Manufacturer: Toyo Keiki
Model: TMW Series
Features
- Industry-first in adopting “Graphic LCD”
The adoption of graphic LCD makes the measurement display screen different from conventional types.
“Display of time series” using a trend graphVarious measurement displays
Not only the conventional straight bar graph but also an arc-shaped bar graph are available. They can switch
Up to 10 elements are display collectively
The display screen can switch among one-element, four-element, and ten-element screens in real time. (See page 6.)
On the ten-element screen, the measurement items of up to 35 elements can display by scrolling the screen (3P4W specification).
Arbitrary VT and CT settings are possible
The VT and CT values on the primary side can set arbitrarily to support special VT and CT.
“Easy setting” (Setting support function provided)
In the setting mode, the operation instruction is display at the bottom of the display screen. Therefore, setting is possible without the manual.
Specifications
Item | Input range | Display |
---|---|---|
Current (R, S, T) | 0~5A (20A extension) | Input current × CT ratio |
Voltage (R-S, S-T, T-R) | 0~150V or 0~300V Note 1) |
voltage × VT ratio |
Active Power | 0~1kW or 0~2kW Note 1) |
Input Power × CT ratio×VT ratio |
Reactive Power | LEAD 1kvar~LAG 1kvar or LEAD 2kvar~LAG 2kvar Note 1) |
Input × CT ratio × VT ratio |
Apparent Power | 0~1kVA or 0~2kVA Note 1) |
× CT ratio × VT ratio |
Power factor | LEAD 0~1.0~LAG 0 Note 1) |
LEAD 0.0~100.0~LAG 0.0% |
Frequency | 45Hz~65Hz | 45.00Hz~65.00Hz |
Watt demand | 0~1kW or 0~2kW Note 1) |
Input × CT ratio × VT ratio |
Amp demand | 0~5A or (20A extension) | Input current × CT ratio |
Active energy | Note 1) | 0.000~999999.999kWh (MWh) Incoming Wh : sign +Wh outgoing Wh : sign -Wh |
Reactive energy | Note 1) | 0.000~999999.999kvarh (Mvarh) LAG 0.000~999999.999kvarh (Mvarh) LEAD 0.000~999999.999kvarh (Mvarh) |
Operating time | 0~999999h | |
Current THD | 0~100% Peak Value : 0~9.9A | 0~100% |
Voltage THD | 0~100%, Peak Value 0~250V (Rated Voltage 110V) 0~500V (Rated Voltage 220V) Note 1) |
0~100% |
note 1) Invalid for current specifications
② Aux. Power
Spec | Voltage range | Consumption |
---|---|---|
Worldwide power | AC80~264V DC80~143V |
5VA 3W (27mA) |
DC24V | DC19~31V | 3W (123mA) |
③ Input specifications
Spec | Rating | Input range | Consumption |
---|---|---|---|
1P2W / 1P3W / 3P3W | 110V/220V, 100V/200V 5A |
0〜150V/0〜300V 0〜5A(extension to 20A) |
0.11VA/0.22VA 0.5VA |
1P2W / 1P3W / 3P3W | 440V 5A |
0〜600V 0〜5A(extension to 20A) |
0.44VA 0.5VA |
3P4W | 110/√3‾V/220/√3‾V 5A |
〜150/√3‾V/0〜300/√3‾V 0〜5A(extension to 20A) |
0.04VA/0.08VA 0.5VA |
3P4W | 440/√‾3V 5A |
0〜600V/√3‾V 0〜5A(extension to 20A) |
0.16VA 0.5VA |
Note) exchange 1P2W, 1P3W, 3P3W spec and 110V, 220V input each other by setting
④ Output specifications
Output type | Specification |
---|---|
Analog output | DC4~20mA 0~550Ω DC1~5V 600Ω~∞ MAX.4CH |
Pulse output | Active energy or Reactive energy DC125V, AC125V 0.1A MAX.2CH |
Relay output | Upper alarm or Lower alarm AC250V 5A DC100V 0.3A, DC30V 5A MAX.2CH |
Transmission output | RS-485 Protocol: MODBUS Baudrate: 2400, 4800, 9600, 19.2k, 38.4kbps |
(Note) Up to two point outputs are available for pulse output and alarm output.
Either of transmission output and pulse output (alarm output) is to be selected (see type name system).
Pulse output is output asynchronously with the display update interval.
Note that a time difference may be generated between the indicated value and the pulse number.
⑤ Remote input specification
The measurement items of the main display can be changed by applying a voltage from outside (Display screen 1 or Display screen 2).
Apply a voltage of 80 to 264 VAC or 80 to 143 VDC to the external input terminal (for 0.5 seconds or more). Each time a voltage is applied, the next item is selected.