Venn WVM-02T type primary pressure regulating valve for fire extinguishing equipment

Manufacturer: Venn Co., Ltd.
Model: WVM-02T

Features

  • Stable operation is easy to achieve by adjusting the needle valve opening to match the usage conditions.
  • In addition, the main valve and pilot valve can be easily disassembled.
  • As a result, maintenance tasks such as adjustment, repair, and parts replacement are simple.
  • Furthermore, the lift-limiting mechanism helps control and limit overflow.

Specifications

Product codeWVM02T-BWVM02T-L
Valve typePrimary pressure control valve for fire extinguishing equipment
UseFor fire extinguishing equipment
Nominal diameter50-150 (2-6)40-150 (1 1/2-6)
Applicable fluidFire extinguishing water
Fluid temperature5-60 ° C
Primary side applied pressure1.6MPa or less
Set pressure adjustment range0.3-1.6MPa
Blow-down pressureSet pressure x 15% or less
AccumulationSet pressure x 10% or less (minimum value 0.03MPa)
End connectionJIS 16K RF flange
Pressure resistance test (water pressure)2.4MPa at water pressure
Mounting postureHorizontal / vertical freedom
Basic valve material bodyFCFCD
Basic valve material Main part Diaphragm discNBR
Basic valve material Main part Valve seatCAC406
Basic valve painting inner surfaceLiquid epoxy resin for water supply
Basic valve painting outer surfaceRed (Munsell 7.5R 4/15)