Japan, NOHMI BOSAI
NOHMI BOSAI FPI012B-1L Series Dedicate Control Panel

Manufacturer: NOHMI BOSAI
 Model: FPI012B-1L Series
Description of FPI012B-1L Series
Nohmi’s infrared three-wavelength flame detector quickly detects fire even in places with ventilation flow, external air, or high ceilings where detection is often difficult for the ordinary detectors.
 This high-sensitivity detector is suitable not only for large spaces but also for outdoor facilities.
Specification
| Type | Dedicated control panel | |
|---|---|---|
| For AC power supply | For DC power supply | |
| Model | FPJ012B-1L–5L-A | FPJ012B-1L–5L-D | 
| Number of circuits | 1 2 3 4 5 | 1 2 3 4 5 | 
| Mounting type | Wall mounting type | |
| Main power supply | AC100V±10%, 50/60Hz | DC24V±10% | 
| Circuit voltage | [Power for the detector, signal-receiving circuit, and display circuit] 24V DC (constant voltage) [IC circuit] 3.3 VDC (constant voltage) | [Power for the detector, signal-receiving circuit, and display circuit] 24V DC (constant voltage) [IC circuit] 3.3 VDC (constant voltage) | 
| Power consumption | Monitoring (VA): 6 11 16 21 26 Alarm in 2 circuits (VA): 11 16 21 26 31 | Monitoring (VA): 8 12 16 20 24 Alarm in 2 circuits (VA): 12 16 20 24 28 | 
| Maximum number of devices | PDCJ001-D, PDCJ002-E Infrared Three-Wavelength Flame Detector: 1unit/circuit | |
| Panel sound | Built-in electronic buzzer (Alarm: Constant, Trouble: Intermittent) | |
| Test & maintenance function | Detector operation test: Manual operation test of the detector (by the test switch) Reset: Reset of detectors and signal-receiving circuits (by the reset switch) Signal cut-off: Cut-off of alarm and trouble output signals (by the signal cut-off switch) Alarm silence: Silence of the control panel (by the alarm silence switch) | |
| Trouble notice function | Automatic open-circuit notice function: Monitors the detector status and the open circuit between the control panel and the detector (The alarm LED blinks when the circuit is open and there is a detector problem) | |
| Signal output | Alarm (latch): All points, 30 VDC, 1 A or less Trouble: 1 point (all points available as an option), 30 VDC, 1 A or less | |
| Alarm detection | Verification: After 2 seconds of detector operation, reset the detector / signal-receiving circuit of the control panel. If during these 13 seconds the control panel experiences no fire, the alarm is judged as fire. Non-verification: The control panel judges it as fire as soon as the alarm signal is received. | |
| Environmental condition | Operating temperature: 0~40°C Operating humidity: 20~85% (RH), No condensation | |
| Maximum cable length | PDCJ001-E: 330 m (when the cable size is φ0.9), 590 m (when the cable size is φ1.2) PDCJ002-E: 560 m (when the cable size is φ0.9), 990 m (when the cable size is φ1.2) | |
| End-of-line resistor | 10 kΩ, 1/2 W (Connected to the terminal in the detector) | |
| Main material | Steel plate t1.2 | |
| Finish | Melamine baking finishing | |
| Dimensions | H400×W350×D170 (mm) | |
| Weight | Max. 15 kg | Max. 14 kg | 

Related Products
-   Organo OLGARD C Series Anti Corrosion Treatment For Cold And Hot Water Systems
-   Kondotec Screw Eye
-   Kyowa Gasket (Type L)
-   Eagle Jack (Konno Corporation) ED-40C-PG-75kM-40 Hydraulic Bottle Jack
-   Eagle Jack (Konno Corporation) G-60T Lever Turning Jaw Toe Jack Share
-   Chino R Series ndustrial Temperature Sensor