Venn RD-57N Pressure Reducing Valve for Door-to-door Water Supply (for water and hot water)

Manufacturer: Venn Co., Ltd.
Model: RD-57N

Features

  • Switching to a key part cartridge can shorten maintenance work and save labor
  • The insulation case is smaller and can be used in smaller places than before.
  • Improved durability by using rubber FKM
  • Inheriting the low noise characteristics that were popular with conventional products
  • Pressure test with pressure reducing valve installed using a test rod

Specifications

Product SymbolRD57N-F
Types of valvesCartridge type door-to-door water supply pressure reducing valve
Nominal diameter20(3/4)
Applicable fluidsTap water and hot water
Fluid temperature5~90°C (5~40°C when using pipe end core)
Primary Side Application Pressure1.0MPa or less
Secondary Side Regulation Pressure Range (Set Pressure)L :0.05~0.10MPa(0.08MPa) M :0.10~0.20MPa(0.15MPa) H :0.20~0.35MPa(0.20,0.25,0.30,0.35MPa)
Nameplate colorL : Green M : Blue H : Red
Maximum Reduction Ratio10:1
Minimum differential pressure before and after the valve0.02MPa
Rated flow rate50L/min (differential pressure 0.1MPa or more)
End connectionJIS G1 Screw
Mounting PositionHorizontal and vertical free
AccessoriesThermal case (self-extinguishing), test rod, pressure gauge fittings (secondary side body installed)
Strainer60 mesh equivalent
Material: BodyCAC406
Material: DiaphragmFKM
Material: DiscFKM

REQUEST QUOTATION

PAYMENT

payment-methods