- Home
- Products
- Hasegawa Electric HP-T Series High Voltage & Special High Voltage Phase Tester Wireless Type
Hasegawa Electric, Japan
Hasegawa Electric HP-T Series High Voltage & Special High Voltage Phase Tester Wireless Type

Made in Japan
Manufacturer: Hasegawa Electric
Model: HP-T Series
With a Short straight type Insulating stick. Easy to use with Wireless pair.

Features
Multi-functional phase tester
Voltage Detection by single detector use, Phase detection with pair detector use.
Measurement is possible on the insulated wire sheathTesting operation is possible through voltage detection terminals or on the wire insulation. *Can not be used on the shielded cable.
Specification
| Model | HP-S3 | HP-S6 | HP-S20 | ||
| Working voltage range | 3.3kV | 6.6kV | 22kV and 33kV | ||
| Frequency | 5Hz or 60Hz [ Either one is to be designated] | ||||
| Phase test function | Discrimination of in-phase or different phases of 120°*Attention: There is no phase sequence [phase rotation] function. | ||||
| Possible distance of phase test | Distance between the transmission side and reception side: Within Sm | ||||
| Insulating stick type | Straight[Short] | ||||
| Total length | without telescopic structure | 550mm | |||
| Indication of operation
| Light
| It shall be able to confirm luminance of 8,000lux. | |||
| Sound | S0dB or more at a distance of 3m | ||||
| Battery | 6R61 or 6F22[9V], each 1pce | ||||
| Operating temperature range | -10°C,—.,+S0°C | ||||
| Structure | Waterproof | ||||
| Weight | 700g ×2 | ||||
| Dielectric strength – Contact tip – Grip | 14kV, 5min | ||||
Dimensions

How to use
Phase checking
By setting the reception side[P1] as a reference, check the transmission side[P2] corresponding to each phase, If there are no sound and light indications, it is a “Different phase”.

Step1
Hang the reception[P1] to any electric circuit, and reception[P1] will emit sound & light.
Step2
Hang the transmission[P2] to any electric circuit, and transmission[P2] will emit only light.
Step3
Keep the transmission[P1] fixed to the circuit, and hang transmission[P2] sequentially to R, S, and T.
Step4
Hang transmission[P2] sequentially, and repeat “Step 3” at all 3 phases.
Accessories
Bag for housing
Other items of Hasegawa Electric
Request the quotation for Hasegawa Electric
Related Products
-

Vessel No.NMC-2PY BIT Magnetizer/Demagnetizer Yellow (2-Piece Set)
-

MIKASA MT-66HRL Tamping Rammer
-

KETT ELECTRIC LABORATORY HX-400 Jute Moisture Tester
-

Sumitomo Super MultiDrill XHGS Type – Solid Carbide Drill For High Efficiency Deep Hole Drilling
-

Kitz PN25 Iron Gate Valve
-

IMADA BC-15 Fixture for Tension Strength Test of Sewed Buttons